15.3 Troubleshooting for Flame Supervision System

COMBAT® CTCU UNIT HEATERS INSTALLATION OPERATION AND SERVICE MANUAL

15.3 Troubleshooting for Flame Supervision System

To measure flame current, connect a 0 - 50 µA DC meter in series with the flame probe. If the meter reads negative values, then reverse the test leads.

NOTE: Minimum flame probe current 1 µA DC.

15.4 Troubleshooting for Solenoid Valves