SECTION 16: REMOVAL AND REPLACEMENT PARTS
16.2 Burner Compartment
Burner
Compartment
Cover
Viewing port for flame probe
Flame Probe
Ignition Electrode |
Remove flexible air duct from spigot
Remove screws and pull off burner cover
The burner compartment is a sealed compartment. Following any work,
16.2.1 Burner Injectors
Burners Injectors
Manifold
Mounting
BracketGromet
Manifold
Remove manifold
screws and pull
out manifold.
Manifold
Unscrew
Injectors
Marking
Ensure gas tight fitting of injectors. Ensure correct alignment with burners. Ensure all pipe joints are gas tight.
MODEL |
|
| ||||||
|
|
|
|
|
|
|
| |
Injector Quantity | 2 |
| 3 | 4 | 5 | 6 | 7 | |
|
|
|
|
|
|
|
| |
Natural Gas (G20) |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Injector size | mm Ø | 1.78 |
| 1.85 | 1.85 | 2.06 | 2.057 | 2.057 |
|
|
|
|
|
|
|
|
|
| in Ø | 0.070 |
| 0.073 | 0.073 | 0.081 | 0.081 | 0.081 |
|
|
|
|
|
|
|
|
|
Marking |
| 50 |
| 49 | 49 | 46 | 46 | 46 |
|
|
|
|
|
|
|
|
|
RG P/N |
| 91930050 |
| 91930049 | 91930049 | 91930046 | 91930046 | 91930046 |
|
|
|
|
|
|
|
| |
Natural Gas (G25) |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
Injector size | mm Ø | 1.99 |
| 2.06 | 2.06 | 2.26 | 2.261 | 2.261 |
|
|
|
|
|
|
|
|
|
| in Ø | 0.0785 |
| 0.081 | 0.081 | 0.089 | 0.089 | 0.089 |
|
|
|
|
|
|
|
|
|
Marking |
| 47 |
| 46 | 46 | 43 | 43 | 43 |
|
|
|
|
|
|
|
|
|
RG P/N |
| 91930047 |
| 91930046 | 91930046 | 91930043 | 91930043 | 91930043 |
|
|
|
|
|
|
|
| |
LPG Propane (G31) and LPG Butane (G30) |
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
Injector size | mm Ø | 1.18 |
| 1.18 | 1.18 | 1.25 | 1.25 | 1.25 |
|
|
|
|
|
|
|
|
|
| in Ø | 0.0465 |
| 0.0465 | 0.0465 | 0.049 | 0.049 | 0.049 |
|
|
|
|
|
|
|
|
|
Marking |
| 56 |
| 56 | 56 | 1.25 | 1.25 | 1.25 |
|
|
|
|
|
|
|
|
|
RG P/N |
| 91930056 |
| 91930056 | 91930056 | 91930125 | 91930125 | 91930125 |
|
|
|
|
|
|
|
|
|
37 of 42