2.5 COMBUSTION AIR AND VENTING COMPONENTS
A.Vent Box: The vent box shall be of [aluminized steel] [409 stainless steel].
B.Flue Fan: Each unit shall have a
C.Combustion Air: For
a piece of flexible duct that terminates at an exterior cabinet flange. Ductwork shall be run from that flange to the building penetration.
D.Flue and Combustion Air Connections: The flue collar and combustion air collar (if applicable) shall be located on the rear of the unit. For Models 30 - 125, heater design shall allow for the shifting of the venting and combustion air collars to the top of the cabinet in the field.
2.6 AXIAL FAN
A.Fan: Each unit is supplied with one (Models
B.Fan Guard: Each axial fan is covered with a fan guard. The guard shall protect against objects ½" (12 mm) and greater in diameter.
C.Motor: The motor shall be an open
control terminal shall allow for
2.8OPTIONS AVAILABLE (Select Applicable Options)
A.
B.Wall Suspension Mounting Bracket Kit (Available for Models
C.Wall Shelf Mounting Bracket Kit (Available for Models
D.Vertical Louver Kit (Available for Models
E.Concentric Vent Kit: The concentric vent kit allows the flue and combustion air to be consolidated into a single concentric vent, thereby minimizing the number of required wall/roof penetrations. The kit consists of a concentric vent box, a 4" (101 mm)vent terminal with baffle plate and a 6" (152 mm) (Models
F.Fuel Conversion Kit: The fuel conversion kit allows for
2.7 CONTROL SYSTEM
A.Factory Testing: The complete control system and burner and gas manifold functions shall be factory tested for proper operation and to simplify field commissioning.
B.Control Enclosure: Burner controls (transformer, ignition module, gas valve, safety switches) shall be internally mounted by the manufacturer. No burner controls or gas train components shall be mounted outside of heater cabinet.
C.Safety Controls:
1.Air Flow Switch: The air flow switch measures air pressure differential across the heat exchangers to verify blower operation and the presence of an adequate supply of combustion air. The gas valve cannot open until the air flow switch is satisfied.
2.High Temperature Limit Switch: The high temperature limit
switch shall turn the burners off when air is discharged above its set point. The switch ensures unit shut down in case of axial fan failure or any problem which may result in overheating.
D.Controls System: Units shall be equipped for use with 120 V / 1 Ø / 60 Hz power supply. All units shall be factory equipped with a 24 V thermostat control terminal strip on the outside of the cabinet,
2.9 PERFORMANCE
A. See Schedule on plans.