GAS-FIRED UNIT HEATER GUIDE SPECIFICATION
PART 1 GENERAL
Provide
1.1SECTION INCLUDES
A. Unit Heater B. Controls
1.2REFERENCES
A.American National Standards Institute (ANSI) / Canadian Standards Association (CSA): Establish requirements applicable to construction, certification and installation of unit heaters.
a.Standard ANSI Z83.8 / CSA 2.6 “Gas Unit Heater and Gas- Fired Duct Furnaces” (latest edition)
B.IAS: Establishes requirements applicable to construction and certification of unit heaters.
a.Standard
C.National Fire Protection Association (NFPA): Establishes fire prevention standards.
a.Article 54: National Fuel Gas Code (latest edition)
b.Article 70: National Electric Code (latest edition)
least 24 months, subject to the manufacturer’s standard warranty limitations.
PART 2: PRODUCTS
2.1 MANUFACTURERS
A.COMBAT® by
2.2 MANUFACTURED UNITS
A.Unit:
1.Separated Combustion: A separated combustion unit shall consist of an enclosed sealed burner box to which combustion air is vented through a piece of internal flexible air duct. This duct terminates at an exterior cabinet flange to which a vent run to the outside of the heated space should be attached.
2.Stainless Steel Heat Exchanger: A stainless steel heat exchanger unit shall consist of heat exchanger tubes, heat exchanger tube supports, heat exchanger tube plates and a vent box produced of 409 stainless steel.
1.3 SUBMITTALS FOR REVIEW
A.Product Data: Provide data with dimensions, service connections, accessories, controls, electrical nameplate data and wiring diagrams.
1.4 PROJECT CLOSEOUT PROCEDURES
A.Training: Provide owner with verbal operating instructions as well as original manufacturer’s installation, operation and service manuals.
1.5 QUALITY ASSURANCE
A.Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section (gas- fired unit heaters) with a minimum of ten years documented experience. Equipment shall be the standard product of the manufacturer and shall have complete catalogued data.
B.Installer Qualifications: All installation and service of unit heaters must be performed by a contractor qualified in the installation and service of said products with proof of a minimum of three years documented experience.
C.Factory Testing: Each unit heater shall be factory tested. Testing shall consist of verification of correct operation of burners, manifold, control assembly and electrical components.
1.6 REGULATORY REQUIREMENTS
A.Conform to ANSI Z83.8 / CSA 2.6, latest edition, and provide evidence that the unit heater and its control system have been found in compliance with these standards by a nationally recognized testing laboratory.
1.7 WARRANTY
2.3 FABRICATION
A.Casing and Components: Galvannealed steel panels, minimum 20 gauge. All panels shall be lined with a minimum of 3/8"(10mm) thick insulation.
B.Access Door: Door shall be provided for easy service of all critical components.
C.Finish: Standard finish is a
D.Louvers: The cabinet shall be equipped with horizontal louvers. Louvers shall be
2.4 HEAT EXCHANGERS, BURNERS AND GAS TRAIN
A.Heat Exchangers: For Models
B.Burners: The burners shall be
C.Gas Train: The gas train is constructed of black pipe and includes a
A. The product shall have a manufacturer’s limited warranty of at