6 Type Tests

6.1 IEC 61850-3 Type Tests

 

Test

 

 

Description

 

 

 

Test Levels

 

 

Severity

 

 

 

 

 

 

 

 

 

Levels

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-2

 

ESD

Enclosure Contact

 

 

+/- 8kV

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enclosure Air

 

 

+/- 15kV

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-3

 

Radiated RFI

Enclosure ports

 

 

20 V/m

 

x

 

 

 

 

 

Signal ports

 

 

+/- 4kV @ 2.5kHz

 

x

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-4

 

Burst (Fast

D.C. Power ports

 

 

+/- 4kV

4

 

 

 

Transient)

A.C. Power ports

 

 

+/- 4kV

4

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports

 

 

+/- 4kV

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

+/- 4kV line-to-earth, +/- 2kV line-to-

4

 

 

 

 

 

 

 

 

line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-5

 

Surge

D.C. Power ports

 

+/- 2kV line-to-earth, +/- 1kV line-to-

3

 

 

 

 

 

line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

+/- 4kV line-to-earth, +/- 2kV line-to-

4

 

 

 

 

 

 

 

 

line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

 

10V

3

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-6

 

Induced

D.C Power ports

 

 

10V

3

 

 

 

(Conducted) RFI

A.C. Power ports

 

 

10V

3

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth ground ports

 

 

10V

3

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-8

 

Magnetic Field

Enclosure ports

 

40 A/m continuous, 1000 A/m for 1 s

 

N/A

 

 

 

 

 

D.C. Power ports

 

30% for 0.1s, 60% for 0.1s, 100% for

 

N/A

 

IEC 61000-4-29

 

 

 

 

0.05s

 

 

 

Voltage Dips &

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30% for 1 period, 60% for 50 periods

 

N/A

 

 

 

 

Interrupts

 

 

 

 

 

IEC 61000-4-11

 

A.C. Power ports

 

100% for 5 periods, 100% for 50

 

N/A

 

 

 

 

 

 

 

 

 

 

 

 

periods2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

2.5kV common, 1kV differential mode

3

 

 

 

 

 

 

 

 

@ 1MHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-12

 

Damped

D.C. Power ports

 

2.5kV common, 1kV differential mode

3

 

 

 

Oscillatory

 

 

@ 1MHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A.C. Power ports

 

2.5kV common, 1kV differential mode

3

 

 

 

 

 

 

 

 

@ 1MHz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-16

 

Mains Frequency

Signal ports

 

30V Continuous, 300V for 1s

4

 

 

 

Voltage

D.C. Power ports

 

30V Continuous, 300V for 1s

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IEC 61000-4-17

 

Ripple on D.C.

D.C. Power ports

 

 

10%

 

3

 

 

 

Power Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dielectric

Signal ports

 

2kVac

(Fail-Safe Relay output)

 

N/A

 

IEC 60255-5

 

D.C. Power ports

 

 

2kVac

 

N/A

 

 

Strength

 

 

 

 

 

 

 

A.C. Power ports

 

 

2kVac

 

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal ports

 

5kV

(Fail-Safe Relay output)

 

N/A

 

IEC 60255-5

 

H.V. Impulse

D.C. Power ports

 

 

5kV

 

N/A

 

 

 

 

 

A.C. Power ports

 

 

5kV

 

N/A

Table 15 - IEC 61850-3 Type Tests

 

27

2007 RuggedCom Inc. All rights reserved

Rev100

Page 27
Image 27
RuggedCom RS910W manual IEC 61850-3 Type Tests