www.RuggedCom.com
6
RuggedVDSLTM RS930L
RuggedVDSL™ RS930L

6-Port Managed Ethernet Switch with Dual Port Ethernet over VDSL Uplinks

EMI and Environmental Type Tests
Notes: 1. Class 2 refers to "Measuring relays and protection equipment for which a very high security margin is required or where the vibration levels are very high,( e.g. shipboard application and for severe transportation conditions")
Environmental Type Tests
Test Description Test Levels Severity Levels
IEC 60068-2-1 Cold Temperature Test Ad -40°C, 16 Hours N/A
IEC 60068-2-2 Dry Heat Test Bd +85°C, 16 Hours N/A
IEC 60068-2-30 Humidity (Damp Heat, Cyclic) Test Db 95% (non-condensing), 55°C , 6
cycles N/A
IEC 60255-21-1 Vibration Tests Fc 2g @ (10 - 150) Hz Class 2
IEC 60255-21-2 Shock Tests Ea 30g @ 11mS Class 2
IEC 61850-3 EMI TYPE TESTS
TEST Description Test Levels Severity Levels
IEC 61000-4-2 ESD Enclosure Contact +/- 8kV 4
Enclosure Air +/- 15kV 4
IEC 61000-4-3 Radiated RFI Enclosure ports 20 V/m x
IEC 61000-4-4 Burst (Fast Transient)
Signal ports +/- 4kV @ 2.5kHz x
D.C. Power ports +/- 4kV 4
A.C. Power ports +/- 4kV 4
Earth ground ports 3+/- 4kV 4
IEC 61000-4-5 Surge
Signal ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
D.C. Power ports +/- 2kV line-to-earth, +/- 1kV line-to-line 3
A.C. Power ports +/- 4kV line-to-earth, +/- 2kV line-to-line 4
IEC 61000-4-6 Induced (Conducted) RFI
Signal ports 10V 3
D.C Power ports 10V 3
A.C. Power ports 10V 3
Earth ground ports 310V 3
IEC 61000-4-8 Magnetic Field Enclosure ports 40 A/m continuous, 1000 A/m for 1 s N/A
IEC 61000-4-29
Voltage Dips & Interrupts
D.C. Power ports 30% for 0.1s, 60% for 0.1s, 100% for 0.05s N/A
A.C. Power ports
30% for 1 period, 60% for 50 periods N/A
IEC 61000-4-11 100% for 5 periods, 100% for 50 periods 2N/A
IEC 61000-4-12 Damped Oscillatory
Signal ports 2.5kV common, 1kV diff. mode@1MHz 3
D.C. Power ports 2.5kV common, 1kV diff. mode@1MHz 3
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz 3
IEC 61000-4-16 Mains Frequency Voltage Signal ports 30V Continuous, 300V for 1s 4
D.C. Power ports 30V Continuous, 300V for 1s 4
IEC 61000-4-17 Ripple on D.C. Power Supply D.C. Power ports 10% 3
IEC 60255-5 Dielectric Strength
Signal ports 2kVac (Fail-Safe Relay output) N/A
D.C. Power ports 2kVac N/A
A.C. Power ports 2kVac N/A
IEC 60255-5 H.V. Impulse
Signal ports 5kV (Fail-Safe Relay output) N/A
D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A
IEEE 1613 (C37.90.x) EMI IMMUNITY TYPE TESTS
Test Description Test Levels Severity Levels
IEEE C37.90.3 ESD Enclosure Contact +/- 8kV N/A
Enclosure Air +/- 15kV N/A
IEEE C37.90.2 Radiated RFI Enclosure ports 35 V/m N/A
IEEE C37.90.1 Fast Transient
Signal ports +/- 4kV @ 2.5kHz N/A
D.C. Power ports +/- 4kV N/A
A.C. Power ports +/- 4kV N/A
Earth ground ports3 +/- 4kV N/A
IEEE C37.90.1 Oscillatory
Signal ports 2.5kV common mode @1MHz N/A
D.C. Power ports 2.5kV common, 1kV diff. mode@1MHz N/A
A.C. Power ports 2.5kV common, 1kV diff. mode@1MHz N/A
IEEE C37.90 H.V. Impulse
Signal ports 5kV (Fail-Safe Relay output) N/A
D.C. Power ports 5kV N/A
A.C. Power ports 5kV N/A
IEEE C37.90 Dielectric Strength
Signal ports 2kVac N/A
D.C. Power ports 2kVac N/A
A.C. Power ports 2kVac N/A