Samsung AR18KPFNDWKNSG, AR24KPFNDWKNSG, AR12KPFNDWKNSG Performing the gas leak tests, English-49

Models: AR18KPFNDWKNSG AR24KPFNDWKNSG AR12KPFNDWKXSG AR12HPFSDWK/SG AR24KPFNDWK/SG AR12KPFNDWKNSG

1 56
Download 56 pages 56.79 Kb
Page 49
Image 49

Performing the gas leak tests

Make sure to check for gas leaks before completing the installation process (connecting the assembly pipe and hose between indoor unit and outdoor unit, insulating the cables, hose and pipe, and fixing the indoor unit to the installation plate).

A C D

B

07stIn llan atio

Test part for outdoor unit

Tightening torque for body cap (Refer to the table)

Spindle

Charging

core

R-22: Diameter of the screw - 7/16-20UNF

R-410A: Diameter of the screw - 1/2-20UNF

Tightening torque for charging port cap (Refer to the table)

To check for gas leaks on the outdoor unit,

Check the valve A and B using a leak detector.

Test part for indoor unit

Before inspecting the leakage, use a torque wrench to close the cap for the service valve. (Comply with a tightening torque for each size of the diameter,and tighten the cap firmly to prevent any leakage.).

To check for any possible leakage, insert inert gas into the pipes connected to indoor/outdoor units and check the connection part of the indoor/outdoor units with soap lather or liquid for leakage test.

Outer

Tightening torque

Diameter

Body cap (N•m)

Charging port cap

(mm)

(N•m)

 

ø 6.35

20 ~ 25

 

ø 9.52

20 ~ 25

 

ø12.70

25 ~ 30

10 ~ 12

ø15.88

30 ~ 35

 

ø19.05

35 ~ 40

 

( 1 N•m = 10 kgf•cm )

To check for gas leaks on the indoor unit,

Check the flare nut C and D using a leak detector.

Leak test with nitrogen (before opening valves)

In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-22.

Leak test (after opening valves)

Before opening valves, discharge all the nitrogen from the system and create vacuum according to page 47~48. After opening valves, check leaks using a leak detector for refrigerant.

Pump down (before disconnecting the refrigerant connections for unit repair, removal or disposal) Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit.

This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

Shut off the liquid valve with the Allen wrench.

Turn the system on in cooling with fan operating at high velocity.

(Compressor will immediately start, provided 3 minutes have elapsed since the last stop).

After 2 minutes of operation, shut the suction valve with the same wrench.

Turn the system off and switch mains supply off.

Disconnect tubing. After disconnection, protect valves and tubing ends from dust.

Compressor damage may occur if run at a negative suction pressure.

English-49

SG_GOOD_A3050_IB&IM_EN_DB68-05200A-03.indd 49

2/2/2016 8:26:29 AM

Page 49
Image 49
Samsung AR18KPFNDWKNSG, AR24KPFNDWKNSG, AR12KPFNDWKNSG, AR24KPFNDWK/SG manual Performing the gas leak tests, English-49

AR18KPFNDWKNSG, AR24KPFNDWKNSG, AR12KPFNDWKXSG, AR12HPFSDWK/SG, AR24KPFNDWK/SG specifications

Samsung's AR series air conditioners, including models AR12KPFNDWKNSG, AR24KPFNDWK/SG, AR12HPFSDWK/SG, AR12KPFNDWKXSG, and AR24KPFNDWKNSG, represent a perfect blend of advanced technology, efficiency, and design, making them a vital component of modern home environments.

One of the standout features of these models is Samsung's Digital Inverter technology. This state-of-the-art system optimizes energy consumption by automatically adjusting the compressor speed depending on the cooling demand. As a result, these air conditioners not only provide powerful cooling when it's needed but also operate quietly and maintain energy efficiency, resulting in lower electricity bills.

Another notable characteristic is the Fast Cooling mode, which allows for rapid temperature adjustments. This is particularly advantageous during the sweltering summer months when immediate relief is desired. The AR series can quickly lower temperatures to provide comfort as soon as you enter the room.

These models also come equipped with Samsung's advanced filtration technology, which plays a significant role in maintaining indoor air quality. The air conditioners are designed with a multi-layer filtration system that traps dust, allergens, and other pollutants, creating a cleaner and healthier environment for occupants. This feature is increasingly essential, particularly for those with allergies or respiratory concerns.

The design of the AR series is sleek and modern, ensuring that they fit seamlessly into any interior decor. The front panel is smooth and simple, often available in neutral colors that allow it to blend effortlessly with various room styles. Furthermore, the compact form factor of these units makes them easy to install without compromising valuable floor space.

In terms of control, these air conditioners are user-friendly. They often come with a remote control for convenient operation from anywhere in the room, as well as smart features that enable control via smartphone apps. This compatibility with smart home systems provides added convenience for tech-savvy users.

Moreover, the models are designed with durability in mind. High-quality components and a robust build ensure that these air conditioners are built to last, handling the rigors of everyday use while minimizing maintenance needs.

In summary, the Samsung AR12KPFNDWKNSG, AR24KPFNDWK/SG, AR12HPFSDWK/SG, AR12KPFNDWKXSG, and AR24KPFNDWKNSG models epitomize modern air conditioning technology. With their efficient performance, advanced filtration, user-friendly controls, and stylish design, they cater to contemporary consumer needs while ensuring comfort and satisfaction.