Sanyo 30KHS82 dimensions Split System Submittal Data, Job Name Location Engineer Submitted to

Models: 30KHS82

1 2
Download 2 pages 6.67 Kb
Page 1
Image 1
Split System Submittal Data

Split System Submittal Data

System: 30KHS82 Indoor/Outdoor: KHS3082/CH3082 Wall Mounted Heat Pump

Job Name:

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

 

General Data (at 230V)

Power

V/PH/Hz

230/208/1/60

Circuit Ampacity

(A)

16.5-18.0

Fuse Size, Max.

(A)

35

Compressor

 

DC Rotary Inverter

No. used

 

1

R.L. Amps - L.R.

(A)

16.5-31.0

Outdoor Unit

 

 

Fan type

 

Propeller

Dia. (in.) - No. Speeds

 

19-9/32-1

Type Drive

 

DC Motor

No. Poles

(RPM)

8 - 750

No. Motors

(W)

1 - 142

CFM

(High)

2060

F.L. Amps

(A)

17.6/16.1

Coil Type

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

 

Slit Plate - Inner Rifled

Rows - F.P.I.

 

2-21.2

Face Area

(sq.ft.)

8.05

Tube Size

(in.)

3/8”

Indoor Unit

 

 

Fan type

 

Cross Flow

Dia. & Length (in.) - No. Speeds

3 - 15/16 L32

No. Speeds

 

3

No. Poles

(RPM, High)

8 - 1370

No. Motors

(W)

47

CFM

(HI/Med/Lo)

630/530/412

Indoor Sound Rating

(Hi) (dB-A)

49

F.L. Amps

(A)

0.4

Coil Type

Aluminum Plate Fin & Copper Tube

Fin Type - Pipe Type

 

Slit Plate - Inner Rifled

Rows - F.P.I.

 

2 - 19.5

Face Area

(sq.ft.)

4.55

Tube Size

(in.)

3/8”

Drain Connection Size

(in.)

1-1/4”

Approval:

Date:

Construction:

Unit #:

Drawing #:

Refrigerant

 

 

 

 

 

R410A

Lbs. - R410a (outdoor unit)

 

 

 

6.5

Control

 

 

 

 

Electric Expansion Valve

Connection

 

 

 

 

 

Flare

Line Length, Max (ft.)

 

 

 

 

 

165

Lift Difference, Max (ft.)

50 (outdoor lower), 100 (outdoor higher)

Line Size

 

 

(in. O.D. Discharge)

3/8”

Line Size

 

 

 

(in. O.D. Suction)

5/8”

Dimensions

 

(in.)

 

H x W x D

Indoor Unit

(Uncrated)

 

11-3/16 x 41-15/16 x 9-1/16

Outdoor Unit

 

(Crated)

 

12-7/32 x 44-7/8 x 14-31/32

(Uncrated)

35-13/16 x 37-1/32 x 13-3/8

 

 

(Crated)

 

 

42-3/8 x 40 x 16-3/8

Weight

 

 

 

Indoor

 

Outdoor

Net

 

(lbs.)

 

32.0

 

185.2

Shipping

 

(lbs.)

 

39.7

 

207.2

Shipping Volume

 

 

 

Indoor

 

Outdoor

 

(cu.ft.)

 

4.59

 

15.88

Performance Data @ ARI Standard Conditions (230/208V)

Cooling

 

 

 

 

 

 

Total Capacity

 

 

 

(BTU/H)

30,600 (10,900-30,600)

Sensible Capacity

 

 

 

(BTU/H)

 

18,600

Latent Capacity

 

 

 

(BTU/H)

 

12,000

SEER

 

 

 

 

 

16

Dehumidification

 

 

 

(Pints/H)

 

9.57

Amps

 

 

 

(A)

 

18-16.5

Power Inputs

 

 

 

(W)

 

3,290

Outdoor Sound Rating

 

 

 

(dB-A)

 

55

Heating

 

 

 

 

 

 

Total Capacity

 

 

 

(BTU/H)

33,000 (14,000-33,000)

HSPF

 

 

 

 

 

9.0

Page 1