Intelligent controller (SHA-KT256EG)
Web application
*Display sample
(Dimensions: H 240 x W 280 x D 138 mm)
*Power supply | AC 100 to 240 V (50 Hz), 20 W |
| (separate power supply) |
*I /O part | Remote input |
| All on/off |
| Remote output |
| All ON, All alarm |
| (external power supply within DC 30 V) |
*Total wiring length | 1 km for each system |
* Only for embedding in the panel
Max. 256 indoor units (4 systems x 64 units) can be controlled. In case of three or
more systems, a communication adapter
ON/OFF, operation mode setting, temperature setting, for speed setting,
air flow direction setting (when used without a remote controller), and remote controller local operation prohibition (prohibition 1, 2, 3, 4) can be done.
A system without a remote controller is possible. Joint use with a remote controller or a system controller etc. also is possible.
Use of a schedule timer and holiday setting also can be done.
Proportional distribution of the
*In case of joint use with a wireless remote control system, there are limitations for the control mode. Please use only with "Permission" and "Prohibition 1".
Limitation contents for prohibited operation
Prohibition means limitation of the operation contents from the remote controller. It is also possible to change the prohibition items.
| Limitation contents |
|
|
| There is no limitation for the operation of the remote controller. However, |
Individual | the contents will be changed to the contents of the controller operated last. |
| |
Prohibition: 1 | The remote controller cannot be used for ON/OFF. (All other |
operations are possible from the remote controller.) | |
|
|
| The remote controller cannot be used for ON/OFF, operation mode |
Prohibition: 2 | change, and temperature setting. (All other operations are possible from |
| the remote controller.) |
| The remote controller cannot be used for operation mode change and |
Prohibition: 3 | temperature setting. (All other operations are possible from the remote |
| controller.) |
Prohibition: 4 | The remote controller cannot be used for operation mode change. |
(All other operations are possible from the remote controller.) | |
|
|
Note: Avoid joint use of the AMY system and the intelligent controller on the same indoor/outdoor operation line.
Linked system No. 1
Intelligent controller
System signal x 4 | Linked system No. 2 |
RS 485 (Polarity shield wire)
Linked system No. 3
Communication
adapter Linked system No. 4
System signal x 4
Max. 4 links can be connected for
the indoor/outdoor operation line= Max. 64 indoor units x 4 (256 units) Max. 30 outdoor units x 4 (120 units)
Communication adaptor (SHA-KA128AGB)
Required to connect three or more linked wiring systems (indoor/outdoor operation lines) to the intelligent controller .
Also required for connection of the AMY software.
* For more detail, please take a look at page 58.
Two linked wiring systems can be connected to one
*As this is not a
(Dimensions: H 260 x W 200 x D 68 mm)
* Power supply: AC 100 to 240 V (50 Hz),
3 W (separate power supply)
CONVENIENT SYSTEM CONTROL