Print Form
ECO-i™ Submittal Data
WCHDZ32053
Heat Recovery: 25 tons VRF Outdoor Unit
Job Name: |
| Approval: |
| ||||||||
Location: |
| Date: |
| ||||||||
Engineer: |
| Construction: |
| ||||||||
Submitted to: |
| Unit #: |
| ||||||||
Submitted by: |
| Drawing #: |
| ||||||||
Reference: |
|
|
|
|
|
|
|
Compressor Warranty: 6 Years
Parts Warranty: 1 Year
Coil Coated to Protect Against Corrosion
Salt Protection also available
Capacities |
| Fan |
|
|
Cooling: Btu/h | 307,200 | Quantity/Type: | 1 Propeller (each) | |
Power Input: KW | 13.3 (each) | Fan Motor Output (KW): | 0.7 | (each) |
Heating: Btu/h | 341,200 |
|
|
|
Power Input: KW | 13.3 (each) | Power Supply |
|
|
|
| V/PH/Hz. | ||
Cooling Mode Nominal Conditions |
| Minimum circuit Amps (MCA): Amps | 59 | (each) |
Indoor: °F DB/°F WB | 80/67 | Max. Overcurrent Protection (MOCP): | 70 | (each) |
Outdoor: °F DB | 95 |
|
|
|
Pipe Length (feet): | 25 | Weight (lbs): | 789 | (each) |
Level Difference (feet): | 0 |
|
|
|
|
| Refrigerant: |
| 410A |
Heating Mode Nominal Conditions |
|
|
|
|
Indoor: °F DB | 70 | Coil |
|
|
Outdoor: °F DB/ °F WB | 47/43 | Coil Face Area (sq. ft.): | 22.5 | (each) |
Pipe Length (feet): | 25 | Number of Rows: | 4 | (each) |
Level Difference (feet): | 0 |
|
|
|
|
| Protection Devices |
|
|
Operating Range |
| High Pressure Switch: |
| Yes |
Cooling: °F DB: | 14 to 113 | Overcurrent (CT Method): |
| Yes |
Heating: °F DB: | Crankcase Heaters (W): | 25 + 32 x 2 (each) | ||
Heating + Cooling °F DB | 14 to 113 |
|
|
|
|
| External Finish: | Electrostatic Powder Coating | |
Compressor |
|
|
|
|
Quantity/Type: 1 Inverter driven rotary & 2 fxed speed scroll (each) |
|
|
| |
Capacity Control Range: |
|
|
|