Split System Submittal Data

Print Form

Split System Submittal Data

System: 26XW72R Indoor/Outdoor: XHW2672R/C2672R

Grille: PNR-XH2442

Ceiling Recessed Air Conditioner

Job Name:

Location:

Engineer:

Submitted to:

Submitted by:

Reference:

 

General Data (at 230V)

Power

V/PH/Hz

230/208/1/60

Circuit Ampacity

(A)

15-30 Indoor-Outdoor

Fuse Size, Max.

(A)

15-30 Indoor-Outdoor

Compressor

 

DC Rotary Inverter

No. used

 

1

R.L. Amps - L.R.

(A)

12.9-17.5

Outdoor Unit

 

 

Fan type

 

Propeller

Dia. (in.) - No. Speeds

 

18-7/64-1

Type Drive - No. Speeds

 

DC Motor

No. Poles

(RPM)

8 - 800

No. Motors

(W)

1 - 90

CFM

(High)

1765

F.L. Amps

(A)

13.8

Coil Type

Aluminum Fin & Copper Pipe

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

1 - 15.9

Face Area

(sq.ft.)

7.26

Tube Size

(in.)

3/8”

Indoor Unit

 

 

Fan type

 

Turbo

Dia. & Length (in.) - No. Speeds

17-7/16-1

No. Speeds

 

3 & Auto

No. Poles

(RPM, High)

6-464

No. Motors

(W)

1 - 40

CFM

(HI/Med/Lo)

710/530/450

Indoor Sound Rating

(Hi) (dB-A)

38

F.L. Amps

(A)

0.7

Coil Type

Aluminum Plate Fin & Copper Tube

Fin Type - Pipe Type

 

Slit Plate - Inner Rifed

Rows - F.P.I.

 

2-14.9

Face Area

(sq.ft.)

3.69

Tube Size

(in.)

9/32”

Drain Connection Size

(in.)

1-17/64

Approval:

Date:

Construction:

Unit #:

Drawing #:

Refrigerant

 

 

 

R410A

Lbs. - R410a (outdoor unit)

 

 

4.19

Control

 

 

Electric Expansion Valve

Connection

 

 

 

Flare

Line Length, Max (ft.)

 

 

 

165

Lift Difference, Max (ft.)

50 (outdoor lower), 100 (outdoor higher)

Line Size

(in. O.D. Discharge)

3/8”

Line Size

(in. O.D. Suction)

5/8”

Dimensions

(in.)

 

H x W x D

Indoor Unit

(Uncrated)

13-5/16 x 33-55/64 x 33-55/64

Outdoor Unit

(Crated)

11-9/64 x 32-7/8 x 33-9/32

(Uncrated)

30-23/32 x 37 x 3-3/8

 

(Crated)

34-31/32 x 39-31/32 x 16-3/32

Weight

Indoor

 

Outdoor

Net

(lbs.)

49

 

128

Shipping

(lbs.)

57

 

148

Shipping Volume

 

Indoor

 

Outdoor

(cu.ft.)

7.1

 

13.0

Performance Data @ ARI Standard Conditions (230/208V)

Cooling

 

 

 

 

Total Capacity

 

(BTU/H)

24,800 (9,500-24,800)

Sensible Capacity

 

(BTU/H)

 

14,810

Latent Capacity

 

(BTU/H)

 

9,990

SEER

 

 

 

14.1

Dehumidification

 

(Pints/H)

 

8.1

Amps

 

(A)

 

15.6/17.3

Power Inputs

 

(W)

 

2,920/2,920

Outdoor Sound Rating

(dB-A)

 

49

Page 1
Image 1