Smart-UPS 750-3000 VA 120/208/230 Vac Rack-mount10
Network Management Card Settings

These settings are available only on units that have a Network Management Card (NMC) and are set in

the factory. These settings can only be modified using an external interface, like the NMC web interface.

NMC IP Address Mode

NMC IP Address

NMC Subnet Mask

NMC Default Gateway

Function Factory Default Options Description
Name String
Outlet Group Outlet Group 1 Edit these names usin g an external interface , such as the Networ k
Management Card Web interface.
UPS Name String UPS Outlets
Turn O n De la y 0 sec Set the value in
seconds The amount of time the UPS or Switched Outlet
Group will wait between receiving the command
to turn on and the actual startup.
Turn Off Delay •0 sec (UPS
Outlets)
•90 sec (Switched
Outlet Groups)
Set the value in
seconds The amount of time that the UPS or Switched
Outlet Group will wait between receiving the
command to turn off and the actual shut down.
Reboot Duration 8 sec Set the value in
seconds The amount of time that the UPS or Switched
Outlet Group must remain off before it will
restart.
Minimum Return
Time 0 sec Set the value in
seconds The amount of battery runtime that must be
available before the UPS or Switched Outlet
Group will turn on.
Load Shed On
Battery Disabled •Shutdown with
Delay
•Shutdown
immediately
•Turn off
immediately
•Turn off with delay
•Disabled
When the unit switches to battery power, the UPS
can disconnect power to the Switched Outlet
Group to save runtime.
Configure this delay time, use the LOAD SHED
TIME WHEN ON BATTERY setting.
Load Shed Time
when On Battery Disabled S et the value in
seconds The amount of time the outlets will function on
battery power before they will turn off.
Load Shed On
Runtime Disabled Shutdown with
delay
•Shutdown
immediately
•Turn off
immediately
•Turn off with delay
•Disabled
When the battery runtime falls below the
specified value, the Switched Outlet Group will
turn off.
Configure this time using the LOAD SHED
RUNTIME REMAINING setting.
Load Shed On
Runtime
Remaining
Disabled Set the value in
seconds When the remaining ru nt im e reaches this level,
the Switched Outlet Group will turn off.
Load Shed on
Overload Disabled • Disabled
•Enabled In the event of an overload (greater than 100%
output), the Switched Outlet Group will
immediately turn off to conserve power for
critical loads. The Switched Outlet Group will
only turn on again with a manual command.