7Smart-UPS 750-3000 VA 120/208/230 Vac Rack-mount
Configuration

UPS Settings

Start-up Settings

Configure these settings at initial start-up, using the display interface or APC PowerChute® software.
Note: During start-up, use the display interface to configure these settings. If nothing is
selected, the unit will use the default settings.

General Settings

Configure these settings at any time, using the display interface or APC PowerChute® software.
Function Factory Default Options Description
Language English •English
•French*
•German*
•Spanish*
• Italian*
•Portuguese*
The language for the display interface.
*Language options will vary by model.
Local Power
Quality Good •Good
•Fair
•Poor
Select the quality of input utility power.
• If G o od is selected, the unit will go on battery
power more often to provide the cleanest power
supply to the connected equipment.
If Poor is selected, the UPS will toler ate more
fluctuations in power and will go on battery power
less often.
If unsure of the local power quality, select Good.
Menu Type Standard Standard or
Advanced The advanced menus include all parameters. The
Standard menus display a limited set of menus and
options.
Function Factory Default Options Description
High Transfer
Point 120 V:
127 Vac 127 Vac
•130 Vac
•133 Vac
•136 Vac To avoid unnecessary battery usage, set the
transfer point higher if the utility voltage is
chronically high and the connected equipment
is known to work under this condition. The
POWER QUALITY setting will automatically
change this settin g.
Note: Use the Advanced Menus to configure
this setting.
208 V:
225 Vac 225 Vac
•229 Vac
•233 Vac
•237 Vac
230 V:
253 Vac 253 Vac
•257 Vac
•261 Vac
•265 Vac