Delta Electronics VFD-VL manual Ground Fault, Over Voltage OV, Ground fault

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 169
Image 169

Chapter 5 Troubleshooting

5.2 Ground Fault

GFF

Ground fault

5.3 Over Voltage (OV)

If output circuit(cable or motor) of AC motor drive is grounded?

Yes

Remove grounding

Maybe AC motor drive has No malfunction or misoperation

due to noise. Please contact DELTA.

Over voltage

Reduce voltage to

No If voltage is within

be within spec.

 

specification

 

 

 

Yes

 

 

 

 

 

 

 

Maybe AC motor drive has malfunction or misoperation due to noise. Please contact with DELTA.

If over-voltage is occurred without load Yes No

No When OV occurs, check if the voltage of DC BUS is greater than protection value

YesYes

No

Reduce moment of inertia

If OV occurs when

Increase

Yes

sudden acceleration

deceleration

 

 

 

stops

 

 

time

 

 

 

 

 

 

Yes

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Increase

Yes

 

 

 

 

 

 

 

acceleration

 

 

 

Increase setting time

 

 

 

 

 

 

 

time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

Need to considerate to

No

 

 

 

 

 

 

 

 

 

 

 

 

Reduce moment of load inertia

use braking unit and

 

 

DC braking

 

No

 

 

 

No

Use braking unit or DC braking

 

 

Yes

 

 

 

 

Need to check control method. Please contact DELTA.

5-2

Revision Nov. 2008, VLE1, SW V1.03

Page 169
Image 169
Delta Electronics VFD-VL manual Ground Fault, Over Voltage OV, Ground fault