Group 5 IM Motor Parameters

 

 

 

 

 

 

Setting

VF

VFPG

SVC

FOCPG

TQCPG

FOCPM

 

 

Pr.

 

Explanation

Settings

Factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05-00

Motor Auto Tuning

0: No function

0

 

 

 

 

 

 

 

 

 

 

1: Rolling test (Rs, Rr, Lm, Lx, no-load current)

 

 

 

 

 

 

 

 

 

 

 

 

2: Static Test

 

 

 

 

 

 

 

 

05-01

Full-load Current of Motor

40-120%

#.##

 

 

05-02

Rated power of Motor

0.00~655.35kW

#.##

 

 

 

 

 

 

 

 

 

 

 

 

 

05-03

Rated speed of Motor (rpm)

0~65535

1710

 

 

 

 

 

 

 

 

 

 

 

 

 

05-04

Number of Motor Poles

2~48

4

 

 

05-05

No-load Current of Motor

0-100%

#.##

 

 

 

05-06

Rs of

Motor

0.000~65.535Ω

0.000

 

 

 

 

05-07

Rr of

Motor

0.000~65.535Ω

0.000

 

 

 

 

05-08

Lm of Motor

0.0~6553.5mH

0.0

 

 

 

 

05-09

Lx of Motor

0.0~6553.5mH

0.0

 

 

 

05-10

Torque Compensation Time

0.001~10.000sec

0.020

 

 

 

 

 

 

 

 

Constant

 

 

 

 

 

 

 

 

05-11

Slip Compensation Time

0.001~10.000sec

0.100

 

 

 

 

 

 

 

 

Constant

 

 

 

 

 

 

 

 

05-12

Torque Compensation Gain

0~10

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05-13

Slip Compensation Gain

0.00~10.00

0.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05-14

Slip Deviation Level

0~1000% (0: disable)

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05-15

Detection Time of Slip

0.0~10.0 sec

1.0

 

 

 

 

 

 

Deviation

 

 

 

 

 

 

 

 

05-16

 

 

0: Warn and keep operation

0

 

 

 

Over Slip Treatment

1: Warn and ramp to stop

 

 

 

 

 

 

 

 

 

 

 

 

2: Warn and coast to stop

 

 

 

 

 

 

 

05-17

Hunting Gain

0~10000 (0: disable)

2000

 

 

 

 

05-18

Accumulative Motor

00~1439

00

 

 

 

 

Operation Time (Min.)

 

 

 

 

 

 

 

 

 

05-19

Accumulative Motor

00~65535

00

 

 

 

 

Operation Time (day)

 

 

 

 

 

 

 

 

05-20

Core Loss Compensation

0~250%

10

 

 

 

 

 

4-10

Revision Nov. 2008, VLE1, SW V1.03