Chapter 4 Parameters

Single-phase input

5

For war d running A

It is helpful for the stable control by inputting correct pulse type.

 

10-03

Encoder Feedback Fault Treatment (PGF1, PGF2)

 

 

 

 

 

 

 

 

Control

VFPG

FOCPG TQCPG

Factory Setting: 2

 

mode

 

 

 

 

 

 

Settings

0

Warn and keep operation

 

 

 

 

1

Warn and RAMP to stop

 

 

 

 

2

Warn and stop operation

 

 

 

 

 

10-04

Detection Time for Encoder Feedback Fault

Unit: 0.1

 

 

 

 

 

 

 

Control

VFPG

FOCPG TQCPG FOCPM

Factory Setting: 1.0

 

mode

 

 

 

 

 

 

Settings

0.0 to 10.0 sec

 

 

 

 

 

 

 

When PG loss, encoder signal error, pulse signal setting error or signal error, if time exceeds the detection time for encoder feedback fault (Pr.10-04), the PG signal error will occur. Refer to the Pr.10-03 for encoder feedback fault treatment.

10-05

Encoder Stall Level (PGF5)

Unit: 1

 

 

 

 

 

Control

VFPG

SVC

FOCPG FOCPM

Factory Setting: 115

mode

 

 

 

 

 

Settings

 

0 to 120% (0: disable)

 

This parameter determines the maximum encoder feedback signal allowed before a fault

occurs. (max. output frequency Pr.01-00 =100%)

 

 

 

 

10-06

Encoder Stall Detection Time

Unit: 0.1

 

 

 

 

 

Control

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.1

mode

 

 

 

 

 

Settings

 

0.0 to 2.0 sec

 

10-07

Encoder Slip Range (PGF7)

Unit: 1

 

 

 

 

 

Control

VFPG

SVC

FOCPG FOCPM

Factory Setting: 50

mode

 

 

 

 

 

Settings

 

0 to 50% (0: disable)

 

Revision Nov. 2008, VLE1, SW V1.03