Chapter 2 Installation and Wiring

„Analog input signals are easily affected by external noise. Use shielded wiring and keep it as short as possible (<20m) with proper grounding. If the noise is inductive, connecting the shield to terminal ACM can bring improvement.

„If the analog input signals are affected by noise from the AC motor drive, please connect a capacitor and ferrite core as indicated in the following diagrams:

ACI/AUI1/AUI2

C

ACM

ferrite core

wind each wires 3 times or more around the core

Digital inputs (FWD, REV, MI1~MI8, COM)

„When using contacts or switches to control the digital inputs, please use high quality components to avoid contact bounce.

Digital outputs (MO1, MO2, MCM)

„Make sure to connect the digital outputs to the right polarity, see wiring diagrams.

„When connecting a relay to the digital outputs, connect a surge absorber or fly-back diode across the coil and check the polarity.

The specification for the control terminals

The Position of External Terminals

 

 

 

 

 

 

 

 

 

 

DCM +E24V

 

 

 

 

 

 

 

 

 

Sink/Source

 

RB

MRC

MRA

 

 

 

 

 

 

mode switch

 

 

 

 

 

 

 

 

 

 

 

MCM

FWD

MI1

MI3

MI5

MI7

COM

AUI1 +10V

ACM

RC

RA

MO1

MO2

REV

MI2

MI4

MI6

MI8

AUI2 -10V

ACI

 

Frame

Torque

Wire

 

C, D, E

8 kgf-cm (6.9 in-lbf)

22-14 AWG (0.3-2.1mm2)

 

Terminal: 0V/24V

1.6 kgf-com(1.4 in-lbf)

30-16 AWG (0.051-1.3mm2)

 

 

Revision Nov. 2008, VLE1, SW V1.03