Chapter 4 Parameters

The parameter is set by the output frequency, current and operation time of the drive for activating the I2t electronic thermal protection function. The function will be activated for the 150% * setting current for the setting of Pr.06-13.

Operation time( min)

 

 

 

5

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

60Hz

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load

 

 

 

0

50 100 150 200

 

fac tor (% )

 

 

 

 

 

06-14

Heat Sink Over-heat (OH) Warning

 

 

Unit: 0.1

Control

VF

VFPG

SVC

FOCPG TQCPG FOCPM

 

 

Factory setting: 85.0

mode

 

 

 

 

 

 

 

 

 

 

Settings

0.0 to 110.0 oC

 

 

 

 

 

 

 

 

06-15

Stall Prevention Limit Level

 

 

Unit: 1

Control

VF

VFPG

SVC

 

 

 

 

Factory setting: 50

mode

 

 

 

 

 

 

 

 

 

 

Settings

0 to 100% (refer to Pr.06-02, Pr.06-03)

When the operating frequency is larger than Pr.01-01, Pr06-02=150%, Pr. 06-03=100% and Pr.

06-15=80%:

Stall Prevention Level during acceleration = 06-02x06-15=150x80%=120%.

Stall Prevention Level at constant speed= 06-03x06-15=100x80%=80%.

Stall Prevention Level

06- 02

 

0 1-0 1

x06- 02

 

output frequency

 

 

 

06-15

 

 

 

 

01-01

frequency

 

 

 

 

4-66

Revision Nov. 2008, VLE1, SW V1.03