Delta Electronics VFD-VL manual Analog input terminals ACI, AUI1, AUI2, ACM

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 37
Image 37

Chapter 2 Installation and Wiring

Terminal

Terminal Function

 

Factory Settings (SINK)

Symbol

 

ON: Connect to DCM

 

 

 

 

Multi-function Output 1

The AC motor drive output every monitor signal,

MO1

such as operational, frequency attained,

(Photocoupler)

 

overload, etc. by open collector transistor. Refer

 

 

 

 

 

 

to Pr.03.01 multi-function output terminals for

 

 

 

details.

 

 

 

 

 

Max: 48Vdc/50m A

 

 

 

 

M O1

 

Multi-function Output 2

 

~

MO2

 

M O2

(Photocoupler)

 

 

 

 

 

 

 

 

internal circuit MCM

 

Analog current Input

Impedance:

250Ω

 

ACI

ACI circuit

Resolution:

12 bits

 

 

 

Range:

4 ~ 20mA/0~10V =

ACI

 

 

 

0 ~ Max. Output Frequency

 

 

 

 

(Pr.01-00)

 

 

 

Set-up:

Pr.03-00 ~ Pr.03-02

 

ACM

internal circuit

 

 

 

Auxiliary analog voltage input

Impedance:

2mΩ

 

+10 V

 

AUI circuit

Resolution:

12 bits

 

-10V

AUI1/

 

 

Range:

-10 ~ +10VDC =

AUI2

AUI

 

 

0 ~ Max. Output Frequency

 

 

 

 

 

 

 

 

(Pr.01-00)

 

ACM

 

Set-up:

Pr.03-00 ~ Pr.03-02

 

 

internal circuit

 

 

ACM

Analog control signal

Common for ACI, AUI1, AUI2

(common)

 

 

 

 

 

*Control signal wiring size: 18 AWG (0.75 mm2) with shielded wire.

Analog input terminals (ACI, AUI1, AUI2, ACM)

2-12

Revision Nov. 2008, VLE1, SW V1.03

Page 37
Image 37
Delta Electronics VFD-VL manual Analog input terminals ACI, AUI1, AUI2, ACM