Chapter 4 Parameters

Group 10 Speed Feedback Control Parameters

 

 

 

 

10-00

PG Signal Type

 

 

 

 

 

Control VFPG

FOCPG TQCPG FOCPM

Factory Setting: 0

mode

 

 

 

Settings

0 No function

 

1ABZ

2ABZ+ Hall

3SIN/COS+Sinusoidal

4SIN/COS+Endat

5SIN/COS

6SIN/COS + Hiperface

When Pr.10-00 is set to 3, encoder will have one sine and one cosine signal for each revolution. The signal must be: 0.75 to 1.2Vpp for the amplitude with phase angle 90°±5 elec. (EX: ERN 1185 ERN 1387)

When setting is 4 or 6, it needs to wait for 2 seconds after applying the power to execute RUN command.

Detection of the electromagnetic pole:

Setting 1 or 5: The AC motor drive will output short circuit to detect the position of the electromagnetic pole. At this moment, the motor will generate a little noise.

Setting 2: The AC motor drive will detect the position of the electromagnetic pole by the UVW signal of encoder.

Setting 3: The AC motor drive will detect the position of the electromagnetic pole by the sine signal of encoder.

Setting 4 or 6: The AC motor drive will detect the position of the electromagnetic pole by the

communication signal of encoder.

 

 

 

 

Reference table for tuning

 

 

 

 

Setting of PG

 

 

 

 

 

 

PG signal type

 

Applicable PG card

Pr.08-00=1

 

Pr.08-00=3

signal type

 

 

 

 

 

 

 

 

 

10-00=1

A, B, Z

 

EMVL-PGABO/ABL

Motor will run

 

Motor will run

 

 

 

 

 

 

 

10-00=2

A, B, Z+U, V, W

 

EMVL-PGABL

Motor will run

 

Motor won’t run

 

 

 

 

 

 

 

10-00=3

SIN/COS+

 

EMVL-PGH01/02

Motor will run

 

Motor will run

Sinusoidal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision Nov. 2008, VLE1, SW V1.03

4-97