Chapter 3 Operation and Start Up

„Motor Auto-tuning: When the Source of the Operation Command is set to digital keypad (Pr.00-15=2, refer to step 1) and setting Pr.05-00=2

Pr.05-00

Motor Auto tuning

0:No function

1:Rolling test (Rs, Rr, Lm, Lx, no-load current)

2:Static Test

NOTE 1: It doesn’t need to release the brake in this auto tuning operation. Please make sure that the electromagnetic valve is ON when it is used between the AC motor drive and motor. When Pr.05-00 is set to 2, no-load current of motor must be entered into Pr.05-05. The warning message “Auto tuning” will be displayed on the digital keypad during tuning until it is finished. Then, the measure result will be saved into Pr.05-06~Pr.05-09.

NOTE 2: It needs to finish motor auto tuning before measuring the angle between magnetic field and PG origin.

PM motor

„Control method: Please set Pr.00-09 to 8.

Pr.00-09 Control Method

0:V/f Control

1:V/f Control + Encoder (VFPG)

2:Sensorless vector control (SVC)

3:FOC vector control + Encoder (FOCPG)

4:Torque control + Encoder (TQCPG)

8: FOC PM control (FOCPM)

„Inputting the nameplate information on the motor into Pr.01-00~01-02 and Pr.08-01~08- 04

Pr.01-0010.00~120.00Hz

Maximum Output Frequency

Pr.01-01

1st Output Frequency Setting 1 (base frequency/motor rated frequency)

0.00~120.00Hz

Pr.01-02

1st Output Voltage Setting 1 (base voltage/motor rated voltage)

230V: 0.1V~255.0V

460V: 0.1V~510.0V

„Motor Auto-tuning: When the Source of the Operation Command is set to digital keypad (Pr.00-15=2, refer to step 1) and setting Pr.08-00=2

Pr.08-00

Motor Auto tuning

0:No function

1:Only for the unloaded motor, auto measure the

Angle between magnetic field and PG origin (08-09)

2:For PM motor parameters

3:Auto measure the Angle between magnetic field and PG origin (08-09)

3-8

Revision Nov. 2008, VLE1, SW V1.03