Delta Electronics VFD-VL manual Step, IM motor

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 46
Image 46

Chapter 3 Operation and Start Up

Settings of Pr.02- 13~02-22

19:Brake chopper output error

20:Warning output

21:Over voltage warning

22:Over-current stall prevention warning

23:Over-voltage stall prevention warning

24:Operation mode indication (Pr.00-15≠0)

25:Forward command

26:Reverse command

27:Output when current >= Pr.02-33

28:Output when current < Pr.02-33

29:Output when frequency >= Pr.02-34

30:Output when frequency < Pr.02-34

31-32: Reserved

33:Zero speed (actual output frequency)

34:Zero speed with Stop (actual output frequency)

35:Error output selection 1 (Pr.06-22)

36:Error output selection 2 (Pr.06-23)

37:Error output selection 3 (Pr.06-24)

38:Error output selection 4 (Pr.06-25)

39:Reserved

40:Speed attained (including zero speed)

41:Reserved

3.3.2.2 Step 2

Motor tuning

„Setting the parameters according to the motor type (PM or IM)

IM motor

„Inputting the nameplate information on the motor into Pr.01-00~01-02 and Pr.05-01~05- 04

Pr.01-0010.00~120.00Hz

Maximum Output Frequency

Pr.01-01

1st Output Frequency Setting 1 (base frequency/motor rated frequency)

0.00~120.00Hz

Pr.01-02

1st Output Voltage Setting 1 (base voltage/motor rated voltage)

230V: 0.1V~255.0V

460V: 0.1V~510.0V

Revision Nov. 2008, VLE1, SW V1.03

3-7