Chapter 4 Parameters

Group 9: Communication Parameters

When the AC motor drive is controlled by RS-485 serial communication, a converter, VFD-USB01 or IFD8500, should be connected between the AC motor drive and PC.

Serial interface 6 1 1: +EV

2:GND

3:SG-

4:SG+

RS-485 5: NC 6: NC

09-00

Communication Address

 

 

 

 

 

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

Factory Setting: 1

mode

 

 

 

 

Settings

1 to 254

 

 

 

 

 

If the AC motor drive is controlled by RS-485 serial communication, the communication address for this drive must be set via this parameter. And the communication address for each AC motor drive must be different and unique.

09-01

Transmission Speed

 

Unit: 0.1

Control

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory Setting: 9.6

mode

 

 

 

 

 

 

 

Settings

4.8 to 115.2kbps

 

 

 

 

This parameter is used to set the transmission speed between the RS485 master (PLC, PC,

etc.) and AC motor drive.

 

 

 

 

 

 

09-02

Transmission Fault Treatment

 

Control

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory Setting: 3

mode

 

 

 

 

 

 

 

Settings

0

 

Warn and keep operating

 

 

 

1

 

Warn and RAMP to stop

 

 

 

2

 

Reserved

 

 

 

3

 

No action and no display

 

 

 

 

 

 

 

 

This parameter is set to how to react if transmission errors occur.

09-03

Time-out Detection

Unit: 0.1

 

 

 

 

 

 

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

Factory Setting: 0.0

 

mode

 

 

 

 

 

Settings

0.0 ~ 100.0 sec (0.0: disable)

 

 

It is used to set the communication time-out time.