Delta Electronics VFD-VL manual 07-05, 07-06, 07-07, 07-08, 07-09, 07-10

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 131
Image 131

Chapter 4 Parameters

 

 

07-05

Start-Point for DC Brake

Unit: 0.01

Control

VF

VFPG

SVC FOCPG

Factory Setting: 0.00

mode

 

 

 

 

 

Settings

 

0.00 to 120.00Hz

 

 

 

 

 

 

This parameter determines the frequency when DC Brake will begin during deceleration. When the setting is less than start frequency (Pr.01-09), start-point for DC brake will begin from the

min. frequency.

Output freque ncy

07-0 3

Run /Stop

 

07-05

DC Brake Time

 

01-09

during St opping

Start-point for

Start

DC brake

 

 

 

 

frequen cy

 

 

 

 

time during

 

 

 

 

 

07-0 4

 

 

 

stopping

 

 

 

ON

 

OFF

Time

 

 

 

 

DC Brake Time

07-06

DC Brake Proportional Gain

Unit: 1

Control

VF

VFPG

SVC

 

Factory Setting: 50

mode

 

 

 

 

 

 

Settings

 

1 to 500Hz

 

It is used to set the output voltage gain when DC brake.

 

 

 

 

 

07-07

Dwell Time at Accel.

 

Unit: 0.01

Control

VF

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.00

mode

 

 

 

 

 

 

Settings

0.00 to 600.00 sec

 

 

 

 

07-08

Dwell Frequency at Accel.

Unit: 0.01

Control

VF

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.00

mode

 

 

 

 

 

 

Settings

0.00 to 120.00 Hz

 

07-09

Dwell Time at Decel.

 

Unit: 0.01

Control

VF

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.00

mode

 

 

 

 

 

 

Settings

0.00 to 600.00 sec

 

 

 

 

07-10

Dwell Frequency at Decel.

Unit: 0.01

Control

VF

VFPG

SVC

FOCPG FOCPM

Factory Setting: 0.00

mode

 

 

 

 

 

 

Settings

0.00 to 120.00 Hz

 

 

 

 

 

 

 

In the heavy load situation, Dwell can make stable output frequency temporarily.

4-76

Revision Nov. 2008, VLE1, SW V1.03