Delta Electronics VFD-VL manual Ea t ES t o p Eeeeee, EEE Fault code 1 E

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 181
Image 181

Chapter 6 Fault Code Information and Maintenance

 

 

Display

 

Description

 

 

 

 

 

 

 

 

 

 

 

DC BUS over-voltage at stop

 

 

 

v Ea t ESt o p EEEEEE

 

Corrective Actions:

 

o

 

 

FEEE F a u l t C o d e : 1 E0

 

1. Check if the input voltage falls within the rated AC

 

 

motor drive input voltage range.

 

 

 

 

2.Check for possible voltage transients.

DC BUS voltage is less than Pr.06-00 during acceleration.

L

v Ea t EAc c e l EEEEE

Corrective Actions:

FEEE Fa u l t C o d e : 1 1E

1. Check if the input voltage is normal

2.Check for possible sudden load

DC BUS voltage is less than Pr.06-00 during deceleration.

L

v Ea t EDe c e l EEEEE

Corrective Actions:

FEEEF a u l t C o d e : 1 E2

1. Check if the input voltage is normal

 

 

2.Check for possible sudden load

DC BUS voltage is less than Pr.06-00 during constant speed.

L

v Ea t ENo r mal ESPD

Corrective Actions:

FEEE F a u l t C o d e : 1 E3

1. Check if the input voltage is normal

2.Check for possible sudden load Low voltage at stop

L

v Ea t ESt o p EEEEEE

Corrective Actions:

FEEEF a u l t Co d e : 1 E4

1. Check if the input voltage is normal

2.Check for possible sudden load Phase loss

 

Ph a s e EL o s s EEEE

Corrective Actions:

 

FEEEF a u l t Co d e : 1 5E

 

Check Power Source Input if all 3 input phases are

 

 

 

connected without loose contacts.

 

 

 

IGBT overheating

 

 

 

IGBT temperature exceeds protection level

 

 

 

1 to15HP: 90 oC

 

 

 

20 to 100HP: 100 oC

 

 

GBT EOv e r EHe a t EE

Corrective Actions:

 

I

1. Ensure that the ambient temperature falls within the

 

F

EEE Fa u l t C o d e : 1E6

specified temperature range.

2.Make sure that the ventilation holes are not obstructed.

3.Remove any foreign objects from the heatsinks and check for possible dirty heat sink fins.

4.Check the fan and clean it.

5.Provide enough spacing for adequate ventilation.

6-4