Chapter 4 Parameters

 

 

 

 

Settings

 

 

Control Mode

 

 

 

 

 

 

VF

VFPG

SVC

FOCPG

TQCPG

FOCPM

 

 

 

32: Middle torque bias (by Pr.07-22)

 

 

33: Low torque bias (by Pr.07-23)

 

 

34-37: Reserved

 

 

 

 

 

 

 

 

 

38: Disable write EEPROM function

 

 

39: Torque command direction

 

 

 

 

 

 

 

 

40: Enable drive function

 

 

41: Reserved

 

 

 

 

 

 

 

 

 

42: Mechanical brake

 

 

43: EPS function

This parameter selects the functions for each multi-function terminal.

If Pr.02-00 is set to 3-wire operation control. Terminal MI1 is for STOP terminal. Therefore, MI1 is not allowed for any other operation.

 

Settings

Functions

Descriptions

0

No Function

 

 

 

 

 

1

Multi-step speed

 

command 1

 

 

 

 

 

 

 

 

2

Multi-step speed

15 step speeds could be conducted through the digital

command 2

 

 

 

statuses of the 4 terminals, and 17 in total if the master

 

 

 

3

Multi-step speed

speed and JOG are included. (Refer to Pr. 04-00~04-14)

command 3

 

 

 

 

 

 

 

 

4

Multi-step speed

 

command 4

 

 

 

 

 

 

 

 

5

Reset

After the error of the drive is eliminated, use this

terminal to reset the drive.

 

 

 

 

 

 

6

JOG Command

JOG operation

 

 

 

 

7

Acceleration/deceleration

When this function is enabled, acceleration and

Speed Inhibit

deceleration is stopped and the AC motor drive starts

 

 

to accel./decel. from the inhibit point.

 

 

 

 

 

 

 

 

 

The 1st, 2nd acceleration

The acceleration/deceleration time of the drive could

8

or deceleration time

be selected from this function or the digital statuses of

 

 

selection

the terminals; there are 4 acceleration/deceleration

 

 

 

speeds in total for selection.

 

 

The 3rd, 4th acceleration

 

 

 

9

or deceleration time

 

 

 

selection

 

 

 

 

 

10

EF Input

External fault input terminal and decelerates by Pr.07-

28. (EF fault will be recorded)

 

 

 

 

 

 

11

Reserved

 

 

 

 

12

Stop output

 

 

 

 

 