Chapter 4 Parameters

Group 2 Digital Input/Output Parameters

 

 

 

 

 

02-00

2-wire/3-wire Operation Control

 

Control

VF

VFPG

SVC FOCPG TQCPG FOCPM

Factory setting: 0

mode

 

 

 

 

 

 

Settings

0

 

FWD/STOP, REV/STOP

 

 

 

1

 

FWD/STOP, REV/STOP (Line Start Lockout)

 

 

 

2

 

RUN/STOP, REV/FWD

 

 

 

3

 

RUN/STOP, REV/FWD (Line Start Lockout)

 

 

 

4

 

3-wire

 

 

 

5

 

3-wire (Line Start Lockout)

 

 

 

 

 

 

 

Three of the six methods include a “Line Start Lockout” feature. When line start lockout is

enabled, the drive will not run once applying the power. The Line Start Lockout feature doesn’t

guarantee the motor will never start under this condition. It is possible the motor may be set in

motion by a malfunctioning switch.

This parameter is used to control operation from external terminals. There are three different

control modes.

02-01

02-00

Control Circuits of the External Terminal

0, 1

FWD/STOP

 

FWD:("OPEN":STOP)

2-wire operation control (1)

 

 

("CLOSE":FWD)

FWD/STOP

REV/STOP

 

REV:("OPEN": STOP)

REV/STOP

 

 

("CLOSE": REV)

 

 

DCM

 

 

 

VFD-VL

2, 3

 

 

FWD:("OPEN":STOP)

2-wire operation control (2)

RUN/STOP

 

 

("CLOSE":RUN)

RUN/STOP

FWD/REV

 

REV:("OPEN": FWD)

REV/FWD

 

 

("CLOSE": REV)

 

 

DCM

 

 

 

VFD-VL

4, 5

 

 

FWD "CLOSE":RUN

3-wire operation control

STOP

RUN

 

 

MI1 "OPEN":STOP

 

 

 

 

REV/FWD

REV/FWD "OPEN": FWD

 

"CLOSE": REV

 

 

 

DCM

 

 

 

VFD-VL

Multi-Function Input Command 1 (MI1) (it is Stop terminal for 3-wire operation)

Factory Setting: 1

Revision Nov. 2008, VLE1, SW V1.03

4-37