Chapter 4 Parameters

4.The rated speed can’t be larger or equal to 120f/p. (f: output frequency Pr.01-01, p: Number of Motor Poles Pr.05-04)

05-01Full-load Current of Motor

Control

VF

VFPG SVC FOCPG TQCPG

Factory setting: #.##

mode

 

 

 

 

Settings

40 to 120%

 

 

 

 

 

This value should be set according to the rated frequency of the motor as indicated on the motor nameplate. The factory setting is 90% X rated current.

Example: if the rated current for 7.5hp (5.5kW) models is 25A and the factory setting is 22.5A. In this way, the current range will be from 10A (25*40%) to 30A (25*120%).

05-02

 

Rated Power of Motor

Unit: 0.01

 

 

 

 

 

 

Factory setting: #.##

Control

SVC

FOCPG

TQCPG

mode

 

 

 

 

 

 

 

Settings

0.00 to 655.35 kW

Factory Setting: #.##

 

 

 

It is used to set rated power of the motor. The factory setting is the power of the drive.

 

 

 

 

05-03

 

Rated Speed of Motor (rpm)

 

Unit: 1

Control

VFPG

SVC

FOCPG TQCPG

Factory setting: 1710

mode

 

 

 

 

 

 

 

Settings

0 to 65535 rpm

 

 

 

 

It is used to set the rated speed of the motor and need to set according to the value indicated

on the motor nameplate.

 

 

 

 

 

05-04

 

Number of Motor Poles

 

Control

VF

VFPG

SVC FOCPG TQCPG

Factory setting: 4

mode

 

 

 

 

 

 

 

Settings

2 to 48

 

 

 

 

 

It is used to set the number of motor poles (must be an even number).

 

 

 

 

 

 

05 - 05

No-load Current of Motor

Unit: Amp

Control

VFPG

SVC

FOCPG TQCPG

Factory setting: #.##

mode

 

 

 

 

 

 

 

Settings

0 to 100%

 

 

 

 

 

 

 

 

The factory setting is 40% X rated current.

4-58

Revision Nov. 2008, VLE1, SW V1.03