Chapter 4 Parameters

When the AC motor drive runs after Pr.02-29 delay time, the corresponding multi-function output terminal (12: mechanical brake release) will be ON. This function should be used with DC brake.

When the AC motor drive stops 12 after Pr.02-30 delay time, the corresponding multi-function output terminal (12: mechanical brake release) will be OFF.

Motor speed/ Output frequenc y

07- 03

 

07- 04

 

DC brake

DC brake

time during

time during

start-up

stopping

DC brake

 

 

DC brake

 

RUN/STOP

Multi -function output

(m echanical br ak e r eleas e) Pr.02- 11 to 02 -22=12

RUNSTOP

02-30 Brake engage delay time when

02-29 Brake release delay timeelevator stops when elevator starts

bounce time of mechanical brake

brake

Mechanical brake engage

Mechanical brake release

brake engage

02-31

Turn On Delay of Magnetic Contact between Drive and Motor

Unit:0.001

 

02-32

Turn Off Delay of Magnetic Contact between Drive and Motor

Unit:0.001

 

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

Factory setting:

 

0.200

 

mode

 

 

 

 

 

 

 

 

 

Settings

0.000~65.000 Sec

 

 

 

 

 

 

After running, it is used with setting 40 of multifunction input terminal and settings 15 of multifunction output terminals. When multifunction output terminals is ON, the drive starts output after Pr.02-31 delay time. When drive stops output, multifunction output terminals will release after Pr.02-32 delay time.

4-48

Revision Nov. 2008, VLE1, SW V1.03