Chapter 4 Parameters

02-33

Output Current Level Setting for External Terminals

Unit:1

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

Factory setting: 0

mode

 

 

 

 

Settings

0~100%

 

 

 

 

 

When output current is >= Pr.02-33, it will activate multi-function output terminal (Pr.02-11 to Pr.02-22 is set to 27).

When output current is < Pr.02-33, it will activate multi-function output terminal (Pr.02-11 to Pr.02-22 is set to 28).

02-34

Output Boundary for External Terminals

Unit:0.01

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

Factory setting: 0.00

mode

 

 

 

 

Settings

0.00~±120.00Hz

 

 

 

 

 

When output frequency is >=02-34, it will activate the multi-function terminal (Pr.02-11 to Pr.02-22 is set to 29).

When output frequency is <02-34, it will activate the multi-function terminal (Pr.02-11 to Pr.02- 22 is set to 30).

02-35

Detection Time of Mechanical Brake

Unit: 0.01

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

Factory setting: 0.00

mode

 

 

 

 

Settings

0.00 ~ 10.00 sec

 

 

 

 

 

When mechanical brake function (setting 42 of Pr.02-01~02-08) is not enabled within this setting time, it will display fault code 64 (MBF) mechanical brake error.

4-50

Revision Nov. 2008, VLE1, SW V1.03