Chapter 3 Operation and Start Up

3.3.2Explanations for the Auto-tuning Steps

3.3.2.1Step 1

Basic parameters settings

„Make sure that Pr.00-00 (identity code of the AC motor drive) corresponds with the nameplate indicated on the AC motor drive.

„Make sure that all parameters are reset to factory setting (Pr.00-02 is set to 9 or 10).

Pr.00-02

 

0: No function

 

Parameter Reset

 

1: Read only

 

 

 

8: Keypad lock

 

 

 

 

 

 

 

9: All parameters are reset to factory settings (50Hz,

 

 

 

220V/380V)

 

 

 

10: All parameters are reset to factory settings (60Hz,

 

 

 

220V/440V)

 

„ Source of the Master Frequency Command: users can set by themselves (Pr.00-14)

Pr.00-14

1: RS-485 serial communication or digital keypad

Source of the

(KPVL-CC01)

 

Master Frequency

2: External analog input (Pr. 03-00)

Command

3: Digital terminals input

 

„ Source of the Operation Command: users can set by themselves (Pr.00-15)

Pr.00-15

1: External terminals

Source of the

2: RS-485 serial communication or digital keypad

Operation

(KPVL-CC01)

Command

 

„MI/MO external terminals settings:

Refer to Pr.02-01~02-08 for setting the external input terminals MI1~MI8.

NOTE: The factory setting of Pr.02-08 is 40 (Enable drive function). Please disable this function if you don’t need to use this function.

Settings of Pr.02-

0: no function

01~02-08

1: multi-step speed command 1

 

 

2: multi-step speed command 2

 

3: multi-step speed command 3

 

4: multi-step speed command 4

 

5: Reset

 

6: JOG command

 

7: acceleration/deceleration speed inhibit

 

8: the 1st, 2nd acceleration/deceleration time selection

 

9: the 3rd, 4th acceleration/deceleration time selection

 

10: EF input (07-28)

 

11: Reserved

 

12: Stop output

 

13: Disable auto accel./decel. function

Revision Nov. 2008, VLE1, SW V1.03