Chapter 4 Parameters

Group 1 Basic Parameters

 

 

 

Unit: 0.01

01-00

Maximum Output Frequency

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

Factory setting: 60.00/50.00

mode

 

 

 

 

Settings

10.00 to 120.00Hz

 

 

 

 

 

This parameter determines the AC motor drive’s Maximum Output Frequency. All the AC motor drive frequency command sources (analog inputs 0 to +10V, 4 to 20mA and -10V to +10V) are scaled to correspond to the output frequency range.

01-01

1st Output Frequency Setting

Unit: 0.01

Control

VF

VFPG

SVC FOCPG TQCPG FOCPM

Factory setting: 60.00/50.00

mode

 

 

 

 

 

Settings

 

0.00~120.00Hz

 

 

 

 

 

 

It is for the base frequency and motor rated frequency.

This value should be set according to the rated frequency of the motor as indicated on the motor nameplate. If the motor is 60Hz, the setting should be 60Hz. If the motor is 50Hz, it should be set to 50Hz.

01-02

1st Output Voltage Setting

Unit: 0.1

Control

VF

VFPG SVC

FOCPG TQCPG FOCPM

 

mode

 

 

 

 

 

Settings

230V series

0.1 to 255.0V

Factory Setting: 220.0

 

 

460V series

0.1 to 510.0V

Factory Setting: 440.0

 

 

 

 

 

It is for the base frequency and motor rated frequency.

This value should be set according to the rated voltage of the motor as indicated on the motor nameplate. If the motor is 220V, the setting should be 220.0. If the motor is 200V, it should be set to 200.0.

There are many motor types in the market and the power system for each country is also difference. The economic and convenience method to solve this problem is to install the AC motor drive. There is no problem to use with the different voltage and frequency and also can amplify the original characteristic and life of the motor.

01-03

2nd Output Frequency Setting

Unit: 0.01

Control

VF

VFPG

Factory setting: 0.50

mode

 

 

 

 

Settings

0.00~120.00Hz

 

 

 

 

 

Revision Nov. 2008, VLE1, SW V1.03

4-29

Page 84
Image 84
Delta Electronics VFD-VL manual 01-01, 01-02, 01-03