Chapter 4 Parameters

Group 6 Protection Parameters

 

 

Pr.

Explanation

Settings

Factory

VF

VFPG

SVC

FOCPG

TQCPG

FOCPM

 

 

 

 

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06-00

Low Voltage Level

160.0~220.0Vdc

180.0

 

320.0~440.0Vdc

360.0

 

 

 

 

06-01

Phase-loss Protection

0: Warn and keep operation

2

 

 

 

 

1: Warn and ramp to stop

 

 

 

 

 

 

 

 

 

 

 

2: Warn and coast to stop

 

 

 

 

 

 

 

06-02

Over-current Stall

00: disable

00

 

 

 

 

 

 

Prevention during

00~250%

 

 

 

 

 

 

 

 

 

 

Acceleration

 

 

 

 

 

 

 

 

06-03

Over-current Stall

00: disable

00

 

 

 

 

 

 

Prevention during Operation

00~250%

 

 

 

 

 

 

 

06-04

Accel./Decel. Time Selection

0: by current accel/decel time

0

 

 

 

 

 

 

of Stall Prevention at

1: by the 1st accel/decel time

 

 

 

 

 

 

 

 

 

 

constant speed

2: by the 2nd accel/decel time

 

 

 

 

 

 

 

 

 

 

 

3: by the 3rd accel/decel time

 

 

 

 

 

 

 

 

 

 

 

4: by the 4th accel/decel time

 

 

 

 

 

 

 

 

 

 

 

5: by auto accel/decel time

 

 

 

 

 

 

 

06-05

Over-torque Detection

0: disable

0

 

 

 

Selection (OT1)

1: over-torque detection during constant speed operation,

 

 

 

 

 

 

 

 

 

 

 

continue to operate after detection

 

 

 

 

 

 

 

 

 

 

 

2: over-torque detection during constant speed operation, stop

 

 

 

 

 

 

 

 

 

 

 

operation after detection

 

 

 

 

 

 

 

 

 

 

 

3: over-torque detection during operation, continue to operate

 

 

 

 

 

 

 

 

 

 

 

after detection

 

 

 

 

 

 

 

 

 

 

 

4: over-torque detection during operation, stop operation after

 

 

 

 

 

 

 

 

 

 

 

detection

 

 

 

 

 

 

 

06-06

Over-torque Detection Level

10~250%

150

 

 

 

(OT1)

 

 

 

 

 

 

 

 

06-07

Over-torque Detection Time

0.0~60.0 sec

0.1

 

 

 

(OT1)

 

 

 

 

 

 

 

 

06-08

Over-torque Detection

0: disable

0

 

 

 

Selection (OT2)

1: over-torque detection during constant speed operation,

 

 

 

 

 

 

 

 

 

 

 

continue to operate after detection

 

 

 

 

 

 

 

 

 

 

 

2: over-torque detection during constant speed operation, stop

 

 

 

 

 

 

 

 

 

 

 

operation after detection

 

 

 

 

 

 

 

 

 

 

 

3: over-torque detection during operation, continue to operate

 

 

 

 

 

 

 

 

 

 

 

after detection

 

 

 

 

 

 

 

 

 

 

 

4: over-torque detection during operation, stop operation after

 

 

 

 

 

 

 

 

 

 

 

detection

 

 

 

 

 

 

 

06-09

Over-torque Detection Level

10~250%

150

 

 

 

(OT2)

 

 

 

 

 

 

 

 

06-10

Over-torque Detection Time

0.0~60.0 sec

0.1

 

 

 

(OT2)

 

 

 

 

 

 

 

 

 

06-11

Current Limit

0~250%

150

 

 

 

 

06-12

Electronic Thermal Relay

0: Inverter motor

2

Selection

1: Standard motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Disable

 

 

 

 

 

 

 

06-13

Electronic Thermal

30.0~600.0 sec

60.0

 

 

 

Characteristic

 

 

 

 

 

 

 

 

06-14

Heat Sink Over-heat (OH)

0.0~110.0

85.0

 

 

 

Warning

 

 

 

 

 

 

 

 

06-15

Stall Prevention Limit Level

0~100% (refer to Pr.06-02, Pr.06-03)

50

 

 

 

 

06-16

Present Fault Record

0: No fault

0

 

06-17

Second Most Recent Fault

1: Over-current during acceleration (ocA)

0

 

 

 

Record

2: Over-current during deceleration (ocd)

 

 

 

 

 

 

 

06-18

Third Most Recent Fault

3: Over-current during constant speed (ocn)

0

4: Ground fault (GFF)

 

 

 

Record

 

 

 

 

 

 

 

 

 

 

5: IGBT short-circuit (occ)

 

 

 

 

 

 

 

06-19

Fourth Most Recent Fault

0

6: Over-current at stop (ocS)

 

 

 

Record

 

 

 

 

 

 

 

 

 

 

7: Over-voltage during acceleration (ovA)

 

 

 

 

 

 

 

06-20

Fifth Most Recent Fault

0

8: Over-voltage during deceleration (ovd)

 

 

 

Record

 

 

 

 

 

 

 

 

 

 

9: Over-voltage during constant speed (ovn)

 

 

 

 

 

 

 

06-21

Sixth Most Recent Fault

0

10: Over-voltage at stop (ovS)

 

 

 

Record

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 