Chapter 4 Parameters

 

07-23

Low Torque Offset

Unit: 0.1

Control

SVC

FOCPG TQCPG FOCPM

Factory Setting: 10.0

mode

 

 

 

 

Settings

0.0 to 100.0%

 

 

 

 

 

When it is set to 3, the source of torque offset will decide to Pr.07-21, Pr.07-22 and Pr.07-23 by the multi-function input terminals setting (19, 20 or 21). The motor rated torque is 100%.

07-24

Forward Motor Torque Limit

Unit: 1

07-25

Forward Regenerative Torque Limit

Unit: 1

07-26

Reverse Motor Torque Limit

Unit: 1

07-27

Reverse Regenerative Torque Limit

Unit: 1

Control

FOCPG TQCPG FOCPM

Factory Setting: 200

mode

 

 

 

 

Settings

0 to 500%

 

 

 

 

 

The motor rated torque is 100%. The settings for Pr.07-24 to Pr.07-27 will compare with Pr.03- 00=5, 6, 7, 8. The minimum of the comparison result will be torque limit.

 

Positive

 

 

torque

Forward motor mode

Reverse motor mode

 

06-11 current limit

 

06-11 current limit

 

 

 

External analog terminals

External analog terminals

Pr.03-00~02

Pr.03-00~02

5: positive torque limit

5: positive torque limit

8: positive/negative torque limit

8: positive/negative torque limit

7: regenerative torque limit

 

The level of torque limit will be

the min. value of following three values

1.torque limit of Pr.07-24 to Pr.07-26

2.Torque limit of external analog terminals

3.Pr.06-11 current limit

 

 

Pr.07-27

Pr.07-24

 

 

 

 

Reverse regenerative

Forward motor

 

 

speed

 

torque limit

torque limit

 

speed

 

Quadrant II

Quadrant I

 

 

 

Quadrant III Quadrant IV

 

 

 

 

Pr.07-26

Pr.07-25

 

 

 

 

Reverse motor

Forward regenerative

 

 

 

 

torque limit

torque limit

 

 

 

External analog terminals

External analog terminals

 

 

Pr.03-00~03-02

Pr.03-00~03-02

 

 

6: negative torque limit

6: negative torque limit

 

 

8: positive/negative torque limit

8: positive/negative torque limit

 

06-11 current limit

Reverse motor modeNegative torque

06-11 current limit

Forward motor mode

4-80

Revision Nov. 2008, VLE1, SW V1.03