Chapter 4 Parameters

07-19

Source of Torque Offset

 

Control

SVC

FOCPG TQCPG FOCPM

Factory Setting: 0

mode

 

 

 

 

 

Settings

0

Disable

 

 

 

1

Analog input

(Pr.03-00)

 

 

2

Torque offset setting (Pr.07-20)

 

 

3

Control by external terminal (by Pr.07-21 to Pr.07-23)

 

 

 

 

 

This parameter is the source of torque offset.

When it is set to 3, the source of torque offset will decide to Pr.07-21, Pr.07-22 and Pr.07-23

by the multi-function input terminals setting (19, 20 or 21).

 

 

02-01~02-08 is set to 19

02-01~02-08 is set to 20

02-01~02-08 is set to 21

 

Torque offset

OFF

OFF

OFF

 

None

 

 

 

 

OFF

OFF

ON

07-25

 

 

 

 

OFF

ON

OFF

07-24

 

 

 

 

OFF

ON

ON

07-25+07-24

 

 

 

 

ON

OFF

OFF

07-23

 

 

 

 

ON

OFF

ON

07-23+07-25

 

 

 

 

ON

ON

OFF

07-23+07-24

 

 

 

 

ON

ON

ON

07-23+07-24+07-25

 

 

 

 

 

07-20

Torque Offset Setting

Unit: 0.1

Control

SVC

FOCPG TQCPG FOCPM

Factory Setting: 0.0

mode

 

 

 

 

Settings

0.0 to 100.0%

 

 

 

This parameter is torque offset. The motor rated torque is 100%.

 

 

 

 

07-21

High Torque Offset

Unit: 0.1

Control

SVC

FOCPG TQCPG FOCPM

Factory Setting: 30.0

mode

 

 

 

 

Settings

0.0 to 100.0%

 

 

 

 

 

 

 

07-22

Middle Torque Offset

Unit: 0.1

Control

SVC

FOCPG TQCPG FOCPM

Factory Setting: 20.0

mode

 

 

 

 

Settings

0.0 to 100.0%

 

 

 

 

 

Revision Nov. 2008, VLE1, SW V1.03

4-79

Page 134
Image 134