Chapter 4 Parameters

 

 

 

 

01-12

Accel. Time 1

 

 

 

Unit: 0.01

01-14

Accel. Time 2

 

 

 

Unit: 0.01

01-16

Accel. Time 3

 

 

 

Unit: 0.01

01-18

Accel. Time 4

 

 

 

Unit: 0.01

Control

VF

VFPG

SVC

FOCPG FOCPM

 

Factory setting: 3.00

mode

 

 

 

 

 

 

 

Settings

0.00~600.00 sec

 

 

 

 

 

 

 

 

01-13

Decel. Time 1

 

 

 

Unit: 0.01

01-15

Decel. Time 2

 

 

 

Unit: 0.01

01-17

Decel. Time 3

 

 

 

Unit: 0.01

01-19

Decel. Time 4

 

 

 

Unit: 0.01

Control

VF

VFPG

SVC

FOCPG FOCPM

 

Factory setting: 2.00

mode

 

 

 

 

 

 

 

Settings

0.00~600.00 sec

 

 

 

 

 

 

01-20

JOG Acceleration Time

 

Unit: 0.01

 

 

 

 

01-21

JOG Deceleration Time

 

Unit: 0.01

Control

VF

VFPG

SVC

FOCPG FOCPM

 

Factory setting: 1.00

mode

 

 

 

 

 

 

 

Settings

0.00~600.00 sec

 

 

 

 

 

 

 

 

 

The Acceleration Time is used to determine the time required for the AC motor drive to ramp from 0Hz to Maximum Output Frequency (Pr.01-00).

The Deceleration Time is used to determine the time require for the AC motor drive to decelerate from the Maximum Output Frequency (Pr.01-00) down to 0Hz.

The Acceleration/Deceleration Time 1, 2, 3, 4 are selected according to the Multi-function Input Terminals settings. The factory settings are acceleration time 1 and deceleration time 1.

The larger against torque and inertia torque of the load and the accel./decel. time setting is less than the necessary value, it will enable torque limit and stall prevention function. When it happens, actual accel./decel. time will be longer than the action above.

4-32

Revision Nov. 2008, VLE1, SW V1.03