Chapter 6 Fault Code Information and Maintenance

6.1 Fault Code Information

The AC motor drive has a comprehensive fault diagnostic system that includes several different alarms and fault messages. Once a fault is detected, the corresponding protective functions will be activated. The following faults are displayed as shown on the AC motor drive digital keypad display. The six most recent faults can be read from the digital keypad or communication.

The AC motor drive is made up by numerous components, such as electronic components, including IC, resistor, capacity, transistor, and cooling fan, relay, etc. These components can’t be used permanently. They have limited-life even under normal operation. Preventive maintenance is required to operate this AC motor drive in its optimal condition, and to ensure a long life.

Basic check-up items to detect if there were any abnormalities during operation are:

„Wait 5 seconds after a fault has been cleared before performing reset via

keypad of input terminal.

„When the power is off after 5 minutes for 22kW models and 10 minutes for 30kW models, please confirm that the capacitors have fully discharged by measuring the voltage between DC+ and DC-. The voltage between DC+ and DC- should be less than 25VDC.

„Only qualified personnel can install, wire and maintain AC motor drives. Please take off any metal objects, such as watches and rings, before operation. And only insulated tools are allowed.

„Never reassemble internal components or wiring.

„Make sure that installation environment comply with regulations without abnormal noise, vibration and smell.

Revision Nov. 2008, VLE1, SW V1.03

6-1

Page 178
Image 178
Delta Electronics VFD-VL manual Fault Code Information and Maintenance