Chapter 3 Operation and Start Up

 

 

 

Pr.07-19

 

0: Disable

Source of Torque

 

 

 

1: Analog input (Pr.03-00)

Offset

 

2: Torque offset setting (Pr.07-20)

 

 

 

 

3: Control by external terminal (by Pr.07-21 to Pr.07-23)

 

 

 

 

 

 

 

Pr.03-03

 

-100.0~100.0%

 

Analog Input Bias 1

 

 

 

(AUI1)

 

 

 

 

 

 

 

 

Pr.03-06

 

0: Zero bias

Positive/negative Bias

 

1: Lower than bias=bias

Mode (AUI1)

 

2: Greater than bias=bias

 

 

 

 

3: The absolute value of the bias voltage while serving as

 

 

the center

 

 

4: Serve bias as the center

 

 

 

 

 

 

 

Pr.03-09

 

-500.0~500.0%

 

Analog Input Gain 1

 

 

 

(AUI1)

 

 

 

 

 

 

 

NOTE: Pr.03-03, 03-06 and 03-09 are used to adjust the analog input signal.

07-19: Source of torque offset

03-00~02: Analog input selections (AUI1/ACI/AUI2)

03-03~05: Analog input bias (AUI1/ACI/AUI2)

03-06~08: AUI1/ACI/A UI2 bias mode

07-19=1

 

Analog input

 

03-00~02

 

 

+

+/-

Bias mode 03-06~08

Bias

03-03~05

Analog input gain

 

Preload

03-09~11

 

 

 

 

 

 

4.Setting of drive stop

Adjusting Pr.01-29, Pr.01-30 and Pr.11-06

Revision Nov. 2008, VLE1, SW V1.03

3-15

Page 54