Delta Electronics VFD-VL manual 03-03, Analog Input Bias 1 AUI1 Unit, 03-04, Settings 100.0~100.0%

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 107
Image 107

Chapter 4 Parameters

Positive torque

 

03-00~02=5

03-00~02=7

Positive torque limit

Regenerative

 

torque limit

 

03-00~02=8

 

Positive/negative torque limit

 

Reverse

Forward

03-00~02=8

03-00~02=7

Positive/negative torque limit

 

Regenerative

 

torque limit

03-00~02=6

 

Negative torque limit

 

Negative Torque

07-19: Source of torque offset

03-00~02: Analog input selections (AUI1/ACI/AUI2)

03-03~05: Analog input bias (AUI1/ACI/AUI2)

03-06~08: AUI1/ACI/A UI2 bias mode

07-19=1

 

Analog input

 

03-00~02

 

 

+

+/-

Bias mode 03-06~08

Bias

03-03~05

Analog input gain

 

Preload

03-09~11

 

 

 

03-03

Analog Input Bias 1 (AUI1)

 

Unit: 0.1

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

 

Factory setting: 0.0

mode

 

 

 

 

 

Settings

-100.0~100.0%

 

 

 

 

 

 

 

It is used to set the corresponding AUI1 voltage of the external analog input 0.

03-04

Analog Input Bias 1 (ACI)

 

Unit: 0.1

Control

VF

VFPG SVC FOCPG TQCPG FOCPM

 

Factory setting: 0.0

mode

 

 

 

 

 

Settings

-100.0~100.0%

 

 

 

 

 

 

 

4-52

Revision Nov. 2008, VLE1, SW V1.03