Chapter 4 Parameters

Pr.07-07 to Pr.07-10 are for heavy load to prevent OV or OC occurs.

Frequency

 

 

 

07-10

07-08

 

07-09

Dwell

Dwell

 

Frequency

 

Dwell Time

Frequency

 

at Decel.

07-07

at Decel.

at Accel.

Dwell Time

 

 

 

at Accel.

 

Time

 

 

 

 

Dwell at accel./decel.

 

 

07-11

Fan Control

 

 

 

 

 

 

 

 

 

 

 

Control

VF

VFPG

SVC FOCPG TQCPG FOCPM

Factory Setting: 2

 

mode

 

 

 

 

 

 

 

Settings

0

 

Fan always ON

 

 

 

 

1

 

1 minute after AC motor drive stops, fan will be OFF

 

 

 

2

 

AC motor drive runs and fan ON, AC motor drive stops and fan OFF

 

 

 

3

 

Fan ON to run when preliminary heat sink temperature attained

 

 

 

4

 

Fan always OFF

 

This parameter is used for the fan control.

When setting to 3, fan will start to run until temperature is less than 40°C if temperature exceeds 40°C.

07-12

Torque Command

Unit: 0.1

Control

TQCPG

 

Factory Setting: 0.0

mode

 

 

 

 

Settings

-100.0 to 100.0% (Pr. 07-14 setting=100%)

 

This parameter is torque command. When Pr.07-14 is 250% and Pr.07-12 is 100%, the actual torque command = 250X100% X motor rated torque.

 

07-13

Torque Command Source

 

 

 

 

 

 

 

 

Control

TQCPG

 

 

Factory Setting: 2

 

mode

 

 

 

 

 

 

Settings

0

Digital keypad

 

 

 

1

RS485 serial communication (RJ-11)

 

 

 

2

Analog signal (Pr.03-00)

 

 

 

 

 

 

Revision Nov. 2008, VLE1, SW V1.03