Delta Electronics VFD-VL manual EEE Fault Co d e 0 9 E

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 180
Image 180

Chapter 6 Fault Code Information and Maintenance

Display

Description

 

 

Ground fault

 

 

Corrective Actions:

 

 

When (one of) the output terminal(s) is grounded, short

 

 

circuit current is more than 50% of AC motor drive rated

G r o u n d EFa u l t EEEE

current, the AC motor drive power module may be damaged.

NOTE: The short circuit protection is provided for AC

FEEE Fa u l

t C o d e : 0E4

motor drive protection, not for protection of the user.

 

 

1.Check the wiring connections between the AC motor drive and motor for possible short circuits, also to ground.

2.Check whether the IGBT power module is damaged.

3.Check for possible poor insulation at the output line. Short-circuit is detected between upper bridge and lower

 

Sh o r t EF a u l t EEEEE

bridge of the IGBT module.

 

FEEE Fa u l t C o d e : 0 E5

Corrective Actions:

 

 

 

Return to the factory

 

 

c Ea t ESt o p EEEEEE

Over-current at stop

 

o

 

 

F

EEEF a u l t Co d e : 0 E6

Corrective Actions:

 

 

 

Return to the factory

 

 

 

DC BUS over-voltage during acceleration (230V: DC 450V;

 

 

 

460V: DC 900V)

 

 

v Ea t E c c e l EEEEE

Corrective Actions:

 

o

1. Check if the input voltage falls within the rated AC

 

F

EEEFa u l t C o d e : 0E7

motor drive input voltage range.

2.Check for possible voltage transients.

3.If DC BUS over-voltage due to regenerative voltage, please increase the Deceleration Time or add an optional brake resistor.

 

 

DC BUS over-voltage during deceleration (230V: DC 450V;

 

 

460V: DC 900V)

 

v Ea t EDe c e l EEEEE

Corrective Actions:

o

1. Check if the input voltage falls within the rated AC

F

EEEF a u l t Co d e : 0 8E

motor drive input voltage range.

2.Check for possible voltage transients.

3.If DC BUS over-voltage due to regenerative voltage, please increase the Deceleration Time or add an optional brake resistor.

 

 

DC BUS over-voltage during constant speed (230V: DC

 

 

450V; 460V: DC 900V)

 

v Ea t ENo r al ESPD

Corrective Actions:

o

1.

Check if the input voltage falls within the rated AC

F

EEEF a u l t Co d e : 0 9E

2.

motor drive input voltage range.

 

 

Check for possible voltage transients.

 

 

3.

If DC BUS over-voltage due to regenerative voltage,

 

 

 

please increase the Deceleration Time or add an

 

 

 

optional brake resistor.

Revision Nov. 2008, VLE1, SW V1.03

6-3

Page 180
Image 180
Delta Electronics VFD-VL manual EEE Fault Co d e 0 9 E, Display Description Ground fault Corrective Actions