Appendix C How to Select the Right AC Motor Drive

model, (to shorten deceleration time only) or increase the capacity for both the motor and the AC Motor Drive.

C.3 How to Choose a Suitable Motor

Standard motor

When using the AC Motor Drive to operate a standard 3-phase induction motor, take the following precautions:

1.The energy loss is greater than for an inverter duty motor.

2.Avoid running motor at low speed for a long time. Under this condition, the motor temperature may rise above the motor rating due to limited airflow produced by the motor’s fan. Consider external forced motor cooling.

3.When the standard motor operates at low speed for long time, the output load must be decreased.

4.The load tolerance of a standard motor is as follows:

Load duty-cycle

torque(%)

25% 40% 60%

100

82

70

 

60

continuous

50

0

3 6

20

60

 

Frequency (Hz)

5.If 100% continuous torque is required at low speed, it may be necessary to use a special inverter duty motor.

6.Motor dynamic balance and rotor endurance should be considered once the operating speed exceeds the rated speed (60Hz) of a standard motor.

7.Motor torque characteristics vary when an AC Motor Drive instead of commercial power supply drives the motor. Check the load torque characteristics of the machine to be connected.