Delta Electronics VFD-VL Summary of Parameter Settings, Parameter can be set during operation

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 57
Image 57

Chapter 4 Parameters

4.1 Summary of Parameter Settings

:The parameter can be set during operation.

Group 0 System Parameters

 

Pr.

Explanation

Settings

Factory

VF

 

VFPG

 

SVC

 

FOCPG

 

TQCPG

 

FOCPM

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00-00

Identity Code of the AC

Read-only

#

motor drive

 

 

 

 

 

 

 

 

 

 

 

 

 

00-01

Rated Current Display of the

Read-only

#

AC motor drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: No function

0

 

 

 

1: Read only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Reset

8: Keypad lock

 

 

 

 

 

 

 

 

 

 

 

 

00-02

9: All parameters are reset to factory settings (50Hz,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220V/380V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10: All parameters are reset to factory settings (60Hz,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220V/440V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Display the frequency command value (LED F)

0

 

 

 

1: Display the actual output frequency (LED H)

 

 

 

 

 

 

 

 

 

 

 

 

00-03

Start-up Display Selection

2: DC BUS voltage

 

 

 

 

 

 

 

 

 

 

 

 

3: Display the output current (A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4: Output voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5: Multifunction display, see Pr.00-04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: Display output current (A)

0

 

 

 

1: Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2: Display output frequency (H)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Display DC-BUS voltage (U)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4: Display output voltage (E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5: Output power factor angle (n)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6: Display output power kW(P)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7: Display actual motor speed in rpm(r)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8: Display estimate output torque kg-m (t)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9: Display PG position (G)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10: Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11: Display AUI1 % (1.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Content of Multi Function

12: Display ACI % (2.)

 

 

 

 

 

 

 

 

 

 

 

 

00-04

13: Display AUI2 % (3.)

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

 

 

 

 

 

 

 

 

 

 

 

14: Display the temperature of heat sink (°C)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15: Display the temperature of IGBT °C (T.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16: The status of digital input ON/OFF (i)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17: The status of digital output ON/OFF (o)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18: Multi-step speed (S)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19: The corresponding CPU pin status of digital input (i.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20: The corresponding CPU pin status of digital output (o.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21-23: Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24: Output AC voltage when malfunction (8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25: Output DC voltage when malfunction (8.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

26: Output frequency when malfunction (h)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27: Output current when malfunction (4)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28: Output frequency command when malfunction (h.)

 

 

 

 

 

 

 

 

 

 

 

 

00-05

User-Defined Coefficient K

Digit 4: decimal point number (0 to 3)

0

Digit 0-3: 40 to 9999

 

 

 

 

 

 

 

 

 

 

 

 

00-06

Software Version

Read-only

#.#

00-07

Password Input

1 to 9998 and 10000 to 65535

0

0 to 2: times of wrong password

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 to 9998 and 10000 to 65535

0

00-08

Password Set

0: No password set or successful input in Pr.00-07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: Password has been set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0: V/f Control

0

 

 

 

1: V/f Control + Encoder (VFPG)

 

 

 

 

 

 

 

 

 

 

 

 

00-09

Control Method

2: Sensorless vector control (SVC)

 

 

 

 

 

 

 

 

 

 

 

 

3: FOC vector control + Encoder (FOCPG)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4: Torque control + Encoder (TQCPG)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8: FOC PM control (FOCPM)

 

 

 

 

 

 

 

 

 

 

 

 

00-10

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

00-11

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

00-12

Carrier Frequency

2~15KHz

12

 

 

 

 

 

4-2

Revision Nov. 2008, VLE1, SW V1.03