Delta Electronics VFD-VL manual 00-02, Factory setting, 00-04, Content of Multi-Function Display

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 76
Image 76
00-03

 

 

 

 

 

Chapter 4 Parameters

 

 

 

 

00-02

Parameter Reset

 

 

Control

VF

VFPG

SVC

FOCPG TQCPG FOCPM

Factory setting: 0

mode

 

 

 

 

 

 

Settings

0

No Function

 

 

 

1

Read Only

 

 

 

8

Keypad Lock

 

 

 

9

All parameters are reset to factory settings (50Hz, 220V/380V)

 

 

10

All parameters are reset to factory settings (60Hz, 220V/440V)

 

 

 

 

 

 

When it is set to 1, all parameters are read only except Pr.00-00~00-07 and it can be used

with password setting for password protection.

This parameter allows the user to reset all parameters to the factory settings except the fault

records (Pr.06-16 ~ Pr.06-21).

50Hz: Pr.01-01 is set to 50Hz and Pr.01-02 is set to 230V or 400V.

60Hz: Pr.01-01 is set to 60Hz and Pr.01-02 is set to 230Vor 460V.

When Pr.00-02=08, the KPVL-CC01 keypad is locked and only Pr.00-02 can be set. To unlock

the keypad, set Pr.00-02=00.

When Pr.00-02 is set to 1, Pr.00-02 setting should be set to 0 before setting to other setting. Start-up Display Selection

Control

VF

VFPG SVC

FOCPG TQCPG FOCPM

Factory setting: 0

mode

 

 

 

 

Settings 0 Display the frequency command value. (LED F)

1Display the actual output frequency (LED H)

2DC BUS voltage

3Display the output current (A)

4Output voltage

5Multifunction display, see Pr.00-04

This parameter determines the start-up display page after power is applied to the drive.

 

00-04

Content of Multi-Function Display

 

 

Control

VF

VFPG SVC

FOCPG TQCPG FOCPM

Factory setting: 0

 

mode

 

 

 

 

Settings 0 Display the output current in A supplied to the motor

1 Reserved

U: Ou t p u t ECu r r e n t SEEEEEEE0 . 0 Amps E

Revision Nov. 2008, VLE1, SW V1.03