Delta Electronics VFD-VL manual AC Reactor AC Input Reactor Recommended Value, Impedance

Models: VFD-VL

1 251
Download 251 pages 18.69 Kb
Page 208
Image 208

Appendix B Accessories

B.4 AC Reactor

B.4.1 AC Input Reactor Recommended Value

460V, 50/60Hz, 3-Phase

kW

HP

Fundamental

Max.

Inductance (mH)

continuous

 

 

Amps

3% impedance

5% impedance

 

 

Amps

 

 

 

5.5

7.5

12

18

2.5

4.2

7.5

10

18

27

1.5

2.5

11

15

25

37.5

1.2

2

15

20

35

52.5

0.8

1.2

18.5

25

35

52.5

0.8

1.2

22

30

45

67.5

0.7

1.2

30

40

55

82.5

0.5

0.85

 

 

 

 

 

 

37

50

80

120

0.4

0.7

 

 

 

 

 

 

45

60

80

120

0.4

0.7

 

 

 

 

 

 

55

75

100

150

0.3

0.45

 

 

 

 

 

 

75

100

130

195

0.2

0.3

 

 

 

 

 

 

B.4.2 AC Output Reactor Recommended Value

230V, 50/60Hz, 3-Phase

kW

HP

Fundamental

Max.

Inductance (mH)

continuous

 

 

Amps

3% impedance

5% impedance

 

 

Amps

 

 

 

5.5

7.5

25

37.5

0.5

1.2

 

 

 

 

 

 

7.5

10

35

52.5

0.4

0.8

 

 

 

 

 

 

11

15

55

82.5

0.25

0.5

 

 

 

 

 

 

15

20

80

120

0.2

0.4

 

 

 

 

 

 

18.5

25

80

120

0.2

0.4

 

 

 

 

 

 

22

30

100

150

0.15

0.3

 

 

 

 

 

 

30

40

130

195

0.1

0.2

 

 

 

 

 

 

37

50

160

240

0.075

0.15

 

 

 

 

 

 

Revision Nov. 2008, VLE1, SW V1.03