B.6 DC Choke Recommended Values

230V DC Choke

 

Input voltage

 

kW

HP

DC Amps

Inductance (mh)

 

 

 

5.5

7.5

32

0.85

 

 

 

7.5

10

40

0.75

 

230Vac

 

11

15

62

Built-in

 

 

15

20

92

Built-in

 

50/60Hz

 

 

 

18.5

25

110

Built-in

 

3-Phase

 

 

 

22

30

125

Built-in

 

 

 

 

 

 

30

40

-

Built-in

 

 

 

37

50

-

Built-in

460V DC Choke

 

 

 

 

 

 

 

 

 

 

 

 

 

Input voltage

 

kW

HP

DC Amps

Inductance (mh)

 

 

5.5

7.5

18

3.75

 

 

7.5

10

25

4.00

 

 

11

15

32

Built-in

 

 

15

20

50

Built-in

 

460Vac

18.5

25

62

Built-in

 

22

30

80

Built-in

 

50/60Hz

 

30

40

92

Built-in

 

3-Phase

 

 

 

 

 

 

 

37

50

110

Built-in

 

 

 

 

 

 

 

 

 

 

45

60

125

Built-in

 

 

 

 

 

 

 

 

55

75

200

Built-in

 

 

75

100

240

Built-in

 

 

 

 

 

 

 

Revision Nov. 2008, VLE1, SW V1.03