Chapter 6Alarms 63230-300-212
Setpoint-Controlled Relay Function s April 2001
©20 01 Schneider Electric All Rights Reser ved
90
Unbalance Voltage:
Pickupand dropout setpoints are entered in tenthsof percent, based on the
percentagedifference between each phase voltage withrespect to the aver-
ageof all phase voltages. For example,enter an unbalance of 7% as 70. The
unbalancevoltage alarm occurs when the phase voltage deviates from the
averageof the phase voltages, by the percentage pickupsetpoint, for the
specifiedpickup delay. The alarm clears when thepercentage difference
betweenthe phase voltage and the averageof all phases remains below the
dropout setpointfor the specified dropout delay (in seconds).
Phase LossCurrent:
Pickupand dropout setpointsare entered in amperes. The phase loss current
alarm occurs when anycurrent value (but not all current values) is equalt o
orbelow the pickup setpoint for the specified pickup delay(in seconds). The
alarm clears when one of the followingis true:
All of the phases remainabove the dropout setpoint for the specified
dropout delay,or
All of the phases dropbelow the phase loss pickup setpoint.
If all of the phasecurrents are equal to or below the pickup setpoint, during
thepickup delay,the phase loss alarm will not activate. This is consideredan
undercurrent condition. It shouldbe handled by configuring the under current
protectivefunctions.
Phase LossVolta ge:
Pickupand dropout setpoints are entered in volts. The phase loss voltage
alarm occurs when anyvoltage value (but not all voltage values)is equal to
orbelow the pickup setpoint for the specified pickup delay(in seconds). The
alarm clears when one of the followingis true:
All of the phases remainabove the dropout setpoint for the specified
dropout delay(in seconds), OR
All of the phases dropbelow the phase loss pickup setpoint.
If all of the phasevoltages are equal to or below the pickup setpoint, during
thepickup delay,the phase loss alarm will not activate. This is consideredan
under voltagecondition. It should be handled by configuring the under
voltageprotective functions.
Reverse Power:
Pickupand dropout setpoints are entered inkilowatts or kVARs.The reverse
poweralarm occurs when thepower flows in a negative direction and
remains ator below the negative pickup valuefor the specified pickup delay
(in seconds).The alarm clears when the power reading remains above the
dropout setpointfor the specified dropout delay (in seconds).
Phase Reversal:
Pickupand dropout setpoints and delays do not applyto phase reversal. The
phasereversal alarm occurs when the phasevoltage rotation differs fromt he
defaultphase rotation. The circuit monitor assumes that an ABC phase
rotationis norm al.If a CBA phase rotation is normal, the user must change
the circuit monitors phase rotation from ABC (default)to CBA. To change the
phase rotationfrom the display,from the main menu select Setup > Meter >
Advanced.For more informationabout changing the phase rotationsetting of
the circuit monitor, refer to Advanced Meter Setupon page 34.