Appendix AAbbreviated Regist er Listing 63230-300-212
Register Listing April 2001
©200 1 Schneider Electric All Rights Reserved
158
3100
Current-Voltage ModuleProduct ID Number
0=Notpresent
1 = Standard CVM
2 = Overrange CVM
3=CVMT
——0to3
3137 CVMT OperatingSystem Firmware Revision
3138 CT Ratio,Phase A Correction Factor 0.00001 -20,000 to 20,000,Default = 0
3139 CT Ratio,Phase B Correction Factor 0.00001 -20,000 to 20,000,Default = 0
3140 CT Ratio,Phase C CorrectionFactor 0.00001 -20,000 to 20,000,Default= 0
3141 CT Ratio,Neutral Correction Factor 0.00001 -20,000to 20,000,Default= 0
3142 PT Ratio, Phase A Correction Factor 0.00001 -20,000to 20,000,Default = 0
3143 PT Ratio, Phase B Correction Factor 0.00001 -20,000to 20,000,Default = 0
3144 PT Ratio, Phase C Correction Factor 0.00001 -20,000 to 20,000,Default = 0
3145 Neutral-GroundCorrectionFactor 0.00001 -20,000 to 20,000,Default = 0
3154 Phase A Current Field Calibrati on Coefficient 0.00001 -20,000to 20,000, Default= 0
3155 Phase B Current Field Calibrati on Coefficient 0.00001 -20,000to 20,000, Default= 0
3156 Phase C Current Field Calibrat ion Coefficient 0.00001 -20,000to 20,000,Default = 0
3157 NeutralCurrent FieldCalibration Coefficient 0.00001 -20,000to 20,000, Default= 0
3158 Phase A Voltage Field Calibration Coef ficient 0.00001 -20,000to 20,000,Default = 0
3159 Phase B Voltage Field Calibration Coef ficient 0.00001 -20,000to 20,000,Default = 0
3160 Phase C Voltage Field Calibration Coeff icient 0.00001 -20,000 to 20,000,Default = 0
3161 Neutral-GroundVoltageField CalibrationCoefficient 0.00001 -20,000 to 20,000,Default = 0
3170
CTPhaseShiftCorrection@1amp
CT phaseshift correction, foruser instrumentation,in the
rangeof -10ºto +10º. A negative shiftsin the lag direction.
——-1,000 to1,000, Default = 0
3171
CTPhaseShiftCorrection@5amps
CT phaseshift correction, foruser instrumentation,in the
rangeof -10ºto +10º. A negative shiftsin the lag direction.
——-1,000 to1,000, Default = 0
3174
CVMT Mode
0=Undefined
1= Waiting for download
2= Waiting for meter initialization
3= Normal operation
4 = Calibration
5 = Firmware download
——0to5
3175
CVMT Diagnostics
Bit 00 = Summary bit
Bit01=InvalidMode
Bit 02 = Read error
Bit03=Writeerror
Bit04=InvalidCVMTfirmwareversion
——0x0000 to 0xFFFF
3176 CVMT Reset F irmware Revision ——0x0000 to 0xFFFF
Tabl e A3:AbbreviatedRegister List
Register
Number Description Scale
Factor Units Register Range
See How Power Factor is Stored in t he Registeron page 128.
Thealternate storage methodfor power factor(PF) is useful for outputtingPF on analog outputs.The PF valueis stored as a positivevalue
between0 and 2,centered around1 (unity). A valueof 0 lagging mapsto 0; -0.999 mapsto 0.999;0.999 leadingmaps to 1.001;and 0 leading
mapsto 2. The alternate PF is alsostored with a scale factor0.001.
Theseconfiguration registersrequire that youenter the setup mode to change the registerscontents. Issuecommand 9020 to enter setup
mode and 9021 to exit setup mode. See Us ing the Command Interface to Cha nge Configuration Regist erson page 187 for instruction s on
howtousethesetup-modecommands.
Quantity available for 4- wire system only. Value set to - 32,768 if not available.