Chapter 5—Input/Output Capabilities 63230-300-212
I/O Options April 2001
©200 1 Schneider Electric All Rights Reserved
70
The circuitmonitor supports a variety of input and output options including:
•Digital Inputs
•Analog Inputs
•Mechanical RelayOutputs
•Solid StateKYZ Pulse Outputs
•Analog Outputs
Thecircuit monitor has one KYZ output as standard.You can expandthe I/O
capabilitiesby adding the optional I/O Extender (IOX) and the digitalI/O
optioncard (IOC-44). Table5–1 lists the many availableI/O options. The I/O
options areexplained in detail in the sections that follow.
Tabl e 5–1: I/ O ExtenderO ptions
I/O Extender Op tions PartNumber
withno preinstalled I/ Os, acceptsup to 8 individual I/O
moduleswith a maximum of 4 analogI /Os IOX
with4 digital inputs (32 Vdc), 2 digital outputs(60 Vdc),
1analogoutput(4–20 mA), an d 1 analog input (0–5Vdc) IOX2411
with4 digital inputs (120 Vac)and 4 analog inputs
(4–20 mA) IOX0404
with 8 digital inputs (120 Vac) IOX08
Individual I/ O Modules Part Nu mber
DigitalI/Os
120Vac input DI120AC
240Vac input DI240AC
32V dcinput (0.2ms turn on) polarized DI32DC
120 Vac output (3.5A max imum) DO120AC
200Vdc output (3.5A maximum) DO200DC
240 Vac output (3.5A max imum) DO240AC
60V dc output(3.5A maximum) DO60DC
AnalogI/Os
0 to5 Vdc analog input AI05
4 to20 mA analog input AI420
4to20mAanalogoutput AO420
The circuit monitor must be eq uipped with the I/O Extender (I OX)to ins tall the
modules.
I/O OPTIONS