Chapter 5Input/Output Capabilities 63230-300-212
I/O Options April 2001
©200 1 Schneider Electric All Rights Reserved
70
The circuitmonitor supports a variety of input and output options including:
Digital Inputs
Analog Inputs
Mechanical RelayOutputs
Solid StateKYZ Pulse Outputs
Analog Outputs
Thecircuit monitor has one KYZ output as standard.You can expandthe I/O
capabilitiesby adding the optional I/O Extender (IOX) and the digitalI/O
optioncard (IOC-44). Table51 lists the many availableI/O options. The I/O
options areexplained in detail in the sections that follow.
Tabl e 51: I/ O ExtenderO ptions
I/O Extender Op tions PartNumber
withno preinstalled I/ Os, acceptsup to 8 individual I/O
moduleswith a maximum of 4 analogI /Os IOX
with4 digital inputs (32 Vdc), 2 digital outputs(60 Vdc),
1analogoutput(420 mA), an d 1 analog input (05Vdc) IOX2411
with4 digital inputs (120 Vac)and 4 analog inputs
(420 mA) IOX0404
with 8 digital inputs (120 Vac) IOX08
Individual I/ O Modules Part Nu mber
DigitalI/Os
120Vac input DI120AC
240Vac input DI240AC
32V dcinput (0.2ms turn on) polarized DI32DC
120 Vac output (3.5A max imum) DO120AC
200Vdc output (3.5A maximum) DO200DC
240 Vac output (3.5A max imum) DO240AC
60V dc output(3.5A maximum) DO60DC
AnalogI/Os
0 to5 Vdc analog input AI05
4 to20 mA analog input AI420
4to20mAanalogoutput AO420
The circuit monitor must be eq uipped with the I/O Extender (I OX)to ins tall the
modules.
I/O OPTIONS