Chapter 6—Alarms

63230-300-212

Alarm Conditions and Alarm Numbers

April 2001

 

 

Table 6–3: List of Default Alarms by Alarm Number

Alarm

Alarm Description

Abbreviated

Test

Units

Scale

Alarm

Number

Display Name

Register

Group

Type

 

 

 

 

 

 

 

 

 

Standard Speed Alarms (1 Second)

 

 

 

 

￿

 

 

 

 

 

 

 

01

Over Current Phase A

Over Ia

1100

Amperes

A

010

 

 

 

 

 

 

 

02

Over Current Phase B

Over Ib

1101

Amperes

A

010

 

 

 

 

 

 

 

03

Over Current Phase C

Over Ic

1102

Amperes

A

010

 

 

 

 

 

 

 

04

Over Current Neutral

Over In

1103

Amperes

B

010

 

 

 

 

 

 

 

05

Over Current Ground

Over Ig

1104

Amperes

C

010

 

 

 

 

 

 

 

06

Under Current Phase A

Under Ia

1100

Amperes

A

020

 

 

 

 

 

 

 

07

Under Current Phase B

Under Ib

1101

Amperes

A

020

 

 

 

 

 

 

 

08

Under Current Phase C

Under Ic

1102

Amperes

A

020

 

 

 

 

 

 

 

09

Current Unbalance, Max

I Unbal Max

1110

Tenths %

010

 

 

 

 

 

 

 

10

Current Loss

Current Loss

3262

Amperes

A

053

 

 

 

 

 

 

 

11

Over Voltage Phase A–N

Over Van

1124

Volts

D

010

 

 

 

 

 

 

 

12

Over Voltage Phase B–N

Over Vbn

1125

Volts

D

010

 

 

 

 

 

 

 

13

Over Voltage Phase C–N

Over Vcn

1126

Volts

D

010

 

 

 

 

 

 

 

14

Over Voltage Phase A–B

Over Vab

1120

Volts

D

010

 

 

 

 

 

 

 

15

Over Voltage Phase B–C

Over Vbc

1121

Volts

D

010

 

 

 

 

 

 

 

16

Over Voltage Phase C–A

Over Vca

1122

Volts

D

010

 

 

 

 

 

 

 

17

Under Voltage Phase A

Under Van

1124

Volts

D

020

 

 

 

 

 

 

 

18

Under Voltage Phase B

Under Vbn

1125

Volts

D

020

 

 

 

 

 

 

 

19

Under Voltage Phase C

Under Vcn

1126

Volts

D

020

 

 

 

 

 

 

 

20

Under Voltage Phase A–B

Under Vab

1120

Volts

D

020

 

 

 

 

 

 

 

21

Under Voltage Phase B–C

Under Vbc

1121

Volts

D

020

 

 

 

 

 

 

 

22

Under Voltage Phase C–A

Under Vca

1122

Volts

D

020

 

 

 

 

 

 

 

23

Voltage Unbalance L–N, Max

V Unbal L-N Max

1136

Tenths %

010

 

 

 

 

 

 

 

24

Voltage Unbalance L–L, Max

V Unbal L-L Max

1132

Tenths %

010

 

 

 

 

 

 

 

25

Voltage Loss (loss of A,B,C, but not all)

Voltage Loss

3262

Volts

D

052

 

 

 

 

 

 

 

26

Phase Reversal

Phase Rev

3228

051

 

 

 

 

 

 

 

27

Over kVA Demand

Over kVA Dmd

2181

kVA

F

011

 

 

 

 

 

 

 

28

Over kW Demand

Over kW Dmd

2151

kW

F

011

 

 

 

 

 

 

 

29

Over kVAR Demand

Over kVAR Dmd

2166

kVAR

F

011

 

 

 

 

 

 

 

30

Over Frequency

Over Freq.

1180

Hundredths of Hertz

010

 

 

 

 

 

 

 

31

Under Frequency

Under Freq.

1180

Hundredths of Hertz

020

 

 

 

 

 

 

 

32

Lagging true power factor

Lag True PF

1163

Thousandths

055

 

 

 

 

 

 

 

33

Leading true power factor

Lead True PF

1163

Thousandths

054

 

 

 

 

 

 

 

34

Lagging displacement power factor

Lag Disp PF

1171

Thousandths

055

 

 

 

 

 

 

 

35

Leading displacement power factor

Lead Disp PF

1171

Thousandths

054

 

 

 

 

 

 

 

36

Over Current Demand Phase A

Over Ia Dmd

1961

Amperes

A

010

 

 

 

 

 

 

 

37

Over Current Demand Phase B

Over Ib Dmd

1971

Amperes

A

010

 

 

 

 

 

 

 

38

Over Current Demand Phase C

Over Ic Dmd

1981

Amperes

A

010

 

 

 

 

 

 

 

39

Over THD Voltage A–N

Over THD Van

1207

Tenths %

010

 

 

 

 

 

 

 

40

Over THD Voltage B–N

Over THD Vbn

1208

Tenths %

010

 

 

 

 

 

 

 

41

Over THD Voltage C–N

Over THD Vcn

1209

Tenths %

010

 

 

 

 

 

 

 

42

Over THD Voltage A–B

Over THD Vab

1211

Tenths %

010

 

 

 

 

 

 

 

Alarm Types are described in Table 6–4 on page 96.

 

 